Denyo DCA-800SPK [11/12] How to select a generator

Denyo DCA-800SPK [11/12] How to select a generator
      
Frequency Hz
EG capacity kVA
Frequency Hz
EG capacity kVA
50
125
42.5
63.8
97
60
150
51
76.5
115
50
200
68
102
151
60
220
76
114
172
50
270
91
136
208
60
300
102
153
231
50
340
115
173
262
60
400
136
204
308
50
100
34.5
51.8
68
60
125
42.5
63.8
97
60
100
34.5
51.8
68
50
80
27. 2
40.8
62
50
65
21.5
32.3
48.8
60
75
25
37. 5
58
50
50
16
24
38.4
60
60
20.5
30.8
46
50
37
12.3
18.5
28.2
60
45
14.9
22.4
34.3
50
20
6.3
9.5
15.7
60
25
7.6
11.4
19.5
50
30
9.4
14.3
23.1
60
35
11.6
17. 5
27.7
 
Frequency Hz
EG capacity kVA
50
450
155
233
351
60
500
175
263
390
50
700
210
315
508
60
800
243
365
575
50
550/554
185
278
432
60
600/610
205
308
460
DCA-400
DCA-300
DCA-220
DCA-15 0
DCA-12 5
DCA-100
DCA-75
DCA-60
DCA-45
DCA-35DCA-25
DCA-13
DCA-15
DCA-20
50
17
5.4
8.2
13.1
60
20
6.3
9.5
15.7
50
10.5
3.4
5.2
8.3
60
13
4.1
6.4
10.2
50
12.5
4
6
9.6
60
15
5
7.5
11. 9
Model
Model
Model
Item
Item
Item
DCA-500
DCA-600/610
DCA-800
Direct startup
Y- startup1
Y- startup2
Motor capacity kW
Direct startup
Y- startup1
Y- startup2
Motor capacity kW
Direct startup
Y- startup1
Y- startup2
Motor capacity kW
50
1000
306
459
734
60
1100
337
505
808
DCA-110 0
HOW TO SELECT
A GENERATOR
Range of motor capacities that can be used with Denyo generators.
Choosing generator output according to motors and other loads is made simple by
referring to the motor capacity range and generator output in this table.
10
Other Options
The following options are also available:
Reverse power relay
For DCA-125 and above.Provided as standard feature for DCA-800, D CA-110 0 SP
AC power meter
For DCA-125 and above.Provided as standard feature for DCA-800, D CA-110 0 SP
Dual-voltage specifications
For DCA-25USI3,45USI2,60ESH,60USH2.Provided as standard feature for
DCA-25ESK,25ESI,45ESI,60ESI2,75SPI,DCA-100 to 800.Not available for
DCA-13LSK,13LSY,15LSK,20LSK,35SPK,DCA -1100SP
Bearing/stator temperature gauge For DCA-125 and above. Provided as
standard feature for DCA-800SPK,800SPM,DCA -1100SP
Lubricant temperature gauge
Provided as standard feature for DCA-220 and above
Overspeed protection device
Provided as standard feature for DCA-600SPK,DCA-610SPM,DCA-800SPK, 800SPM,
DCA -1100 SP
Keyed fuel tank cap
For DCA-13 to 1100
Mounting of muffler flange
Other options for different ranges and operating capabilities are available. Please feel free to
consult with Denyo.
* Some options may not be available depending upon the model. Confirm the details with a
Denyo sales person.
Motor usage examples in the above table are benchmark values : generator capacity will differ according to
the required momentary voltage drop, motor load factor, and size of startup capacity, as well as motor age
and efficiency.
Notes
Momentary voltage drop when a motor starts up is assumed to be within 30% of no- load voltage.
Motor startup kVA is assumed to be 7kVA per 1kW.
Motor efficiency is assumed to be 85%, and load factor about 90%.
Values shown for Y- startup1and Y- startup2are open and closed, respectively; needed generator capacity differs depending on
startup state.
Not appropriate for determining the capacity of emergency generating equipmentespecially disaster-prevention generating equipment.