9-9. Additional refrigerant charge
Charge refrigerant in a liquid state.
- Charging refrigerant in the gaseous state will change the composition of the refrigerant and lead
to a performance drop.
Do not use a charging cylinder when charging refrigerant.
- The use of a charging cylinder may change the composition of the refrigerant and lead to a
performance drop.
The amount of refrigerant that is shown in the table below is factory-charged in the outdoor units. The amount
necessary for extended piping is not included and needs to be added on site.
Unit model Factory-charged amount [kg (oz)] Unit model Factory-charged amount [kg (oz)]
P200 6.5 (230) P400 11.5 (406)
P250 8.0 (283) P450 11.8 (417)
P300 11.5 (406) P500 11.8 (417)
P350 11.5 (406)
The amount of refrigerant that is shown in the table below is the maximum amount to be added on site.
Unit model Maximum amount to be added [kg (oz)] Unit model Maximum amount to be added [kg (oz)]
P200YKB-A1 22.3 (786) P400YSKB-A1 45.0 (1589)
P250YKB-A1 29.7 (1048) P450YSKB-A1 45.9 (1621)
P300YKB-A1 32.7 (1152) P500YSKB-A1 47.0 (1659)
P350YKB-A1 33.6 (1184) P550YSKB-A1 51.3 (1811)
P400YKB-A1 37.2 (1311) P600YSKB-A1 53.9 (1900)
P450YKB-A1 45.0 (1589) P650YSKB-A1 56.5 (1992)
P500YKB-A1 45.9 (1621) P700YSKB-A1 68.9 (2430)
P750YSKB-A1 68.9 (2430)
P800YSKB-A1 71.4 (2519)
P850YSKB-A1 73.2 (2583)
P900YSKB-A1 75.7 (2671)
P950YSKB-A1 96.9 (3421)
P1000YSKB-A1 99.9 (3527)
P1050YSKB-A1 102.9 (3634)
P1100YSKB-A1 106.0 (3740)
P1150YSKB-A1 109.0 (3847)
P1200YSKB-A1 112.0 (3954)
P1250YSKB-A1 112.0 (3954)
P1300YSKB-A1 112.0 (3954)
P1350YSKB-A1 112.0 (3954)
Both refrigerant overcharge and undercharge will cause problems. Charge the system with the proper amount of
refrigerant.
Record the added refrigerant amount on the label attached to the control box panel for future servicing.