FSP Proline 3/1 30K — руководство по отключению и обслуживанию параллельных систем ИБП [26/48]
![FSP Proline 3/1 20K [26/48] 6 abbreviation meaning in lcd display](/views2/1380774/page26/bg1a.png)
23
bypass breaker.
3) After it shuts down, you can turn off the battery breaker (for long-run model) and remove the
parallel and share current cables. And then remove the unit from the parallel system.
Second method:
1) If the bypass is abnormal, you can not remove the UPS without interruption. You must cut off the
load and shut down the system first.
2) Make sure the bypass setting is enabled in each UPS and then turn off the running system. All UPSs
will transfer to Bypass mode. Remove all the maintenance bypass covers and set the maintenance
switches from “UPS” to “BPS”. Turn off all the input breakers and battery breakers in parallel system.
3) Turn off the output breaker and remove the parallel cable and share current cable of the UPS which
you want to remove. Then, remove it from parallel system.
4) Turn on the input breaker of the remaining UPS and the system will transfer to Bypass mode. Set
the maintenance switches from “BPS” to “UPS and put the maintenance bypass covers back.
5) Turn on the remaining UPS according to the previous section.
Warning:
● Before turning on the parallel system to activate inverter, make sure that all unit’s maintenance switch
at the same position.
● When parallel system is turned on to work through inverter, please do not operate the maintenance
switch of any unit.
3-6. Abbreviation Meaning in LCD Display
Abbreviation
Display content
Meaning
ENA
Enable
DIS
Disable
ATO
Auto
BAT
Battery
NCF
Normal mode (not CVCF mode)
CF
CVCF mode
SUB
Subtract
ADD
Add
ON
On
OFF
Off
FBD
Not allowed
OPN
Allow
RES
Reserved
N.L
Neutral line loss
CHE
Check
OP.V
Output voltage
PAR
Parallel, 001 means the first UPS
L1
The first phase
Содержание
- Table of contents p.3
- 1 transportation and storage p.4
- Safety and emc instructions p.4
- 3 installation p.4
- 2 preparation p.4
- Connection warnings p.5
- 6 standards p.6
- 5 operation p.6
- Installation and operation p.7
- Diagram1 10k 10kl rear panel diagram 2 15kl 20kl rear panel p.7
- 2 rear panel view p.7
- 1 unpacking and inspection p.7
- Output terminal p.10
- Input output terminal p.10
- Diagram 15 battery pack rear panel p.10
- Diagram 13 15kr l 20kr l rear panel diagram 14 15kr l 20k l p.10
- Diagram 11 10kr l rear panel diagram 12 10kr l input p.10
- 3 single ups installation p.11
- 4 ups installation for parallel system p.14
- Wiring diagram of parallel system for 10k 10kl p.15
- Wiring diagram of parallel system for 15k l 20k l p.16
- Wiring diagram of parallel system for 30k p.17
- Share current cable connection p.18
- Parallel communication port connection p.18
- For optimal computer system protection install ups monitoring software to fully configure ups shutdown p.19
- 5 software installation p.19
- 4 single ups operation p.22
- 3 audible alarm p.22
- 5 parallel operation p.25
- 6 abbreviation meaning in lcd display p.26
- 7 lcd setting p.27
- 8 operating mode status description p.37
- 9 fault code p.42
- 10 warning indicator p.43
- Utility extremely unbalanced p.43
- Bypass unstable p.43
- 11 warning code p.43
- Trouble shooting p.44
- Storage and maintenance p.46
- 2 maintenance p.46
- 1 storage p.46
- Specifications p.47
Похожие устройства
-
FSP Proline 3/3 30KИнструкция по эксплуатации -
FSP Proline 3/3 20KИнструкция по эксплуатации -
FSP Proline 3/3 15KИнструкция по эксплуатации -
FSP Proline 3/3 10KИнструкция по эксплуатации -
FSP Proline 3/1 20KИнструкция по эксплуатации -
FSP Proline 3/1 15KИнструкция по эксплуатации -
FSP Proline 3/1 10KИнструкция по эксплуатации -
FSP Knight PRO + RM 6KИнструкция по эксплуатации -
FSP Knight PRO + RM 10KИнструкция по эксплуатации -
FSP Knight PRO+ 1KИнструкция по эксплуатации -
FSP Knight PRO+ 2KИнструкция по эксплуатации -
FSP Knight PRO+ 3KИнструкция по эксплуатации
Узнайте, как правильно отключить и обслуживать параллельные системы ИБП. Следуйте пошаговым инструкциям для безопасного выполнения операций.