FSP Proline 3/1 30K [43/48] Utility extremely unbalanced

FSP Proline 3/1 30K [43/48] Utility extremely unbalanced
40
3-10.Warning Indicator
Warning
Icon (flashing)
Alarm
Battery low
Beeping every second
Overload
Beeping twice every second
Battery unconnected
Beeping every second
Over charge
Beeping every second
EPO enable
Beeping every second
Fan failure/Over temperature
Beeping every second
Charger failure
Beeping every second
I/P fuse broken
Beeping every second
Other warnings (Refer to 3-11)
Beeping every second
3-11. Warning Code
Warning code
Warning event
Warning code
Warning event
01
Battery unconnected
10
L1 IP fuse broken
02
IP Neutral loss or IP L2/L3
fuse broken
21
Line situations are different in parallel
system
04
IP phase abnormal
22
Bypass situations are different in
parallel system
05
Bypass phase abnormal
33
Locked in bypass after overload 3
times in 30min
07
Over charge
34
Converter current unbalance
08
Low battery
35
Battery fuse broken
09
Overload
36
Inverter inter-current unbalance
0A
Fan failure
3A
Cover of maintain switch is open
0B
EPO enable
3B
Phase auto adapt failure
0D
Over temperature
3C
Utility extremely unbalanced
0E
Charger failure
3D
Bypass unstable
Скачать