33
alarm will NOT be muted automatically and the UPS will NOT go
back to normal mode automatically.
Here, you must mute the alarm and make the UPS go back to
normal mode manually. The operation is: Firstly, enter this menu
and press the “Enter” key to make the “CHE” flash. Secondly, press
the “Enter” key again to activate the neutral detection (check). If
neutral is detected, the alarm will be muted and the UPS will go
back to normal mode. If neutral is not detected, the UPS will
continue alarming and stay on the latest status until the neutral is
detected well at next manual checking operation.
CHE is default setting.
13: Battery voltage calibration
Interface
Setting
Parameter 2: Select “Add” or “Sub” function to adjust battery
voltage to real figure.
Parameter 3: the voltage range is from 0V to 9.9V and the
default value is 0V.
14: Charger voltage adjustment
Interface
Setting
Parameter 2: you may choose Add or Sub to adjust charger
voltage
Parameter 3: the voltage range is from 0V to 7.0V and the
default value is 0V.
NOTE:
*Before making voltage adjustment, be sure to disconnect all
batteries first to get the accurate charger voltage.
* Any modification should be suitable to battery specifications.
15: Inverter A voltage adjustment**
Interface
Setting
Parameter 2: you may choose Add or Sub to adjust inverter A
voltage.
Parameter 3: the voltage range is from 0V to 9.9V and the
default value is 0V.
16: Inverter B voltage adjustment**
Interface
Setting
Parameter 2: you may choose Add or Sub to adjust inverter B
voltage*.
Parameter 3: the voltage range is from 0V to 9.9V and the
default value is 0V.
*It will display number 1 under or to represent
inverter B voltage.