FSP Proline 3/3 10K — решение проблем с источниками бесперебойного питания [33/36]
![FSP Proline 3/3 30K [33/36] Trouble shooting](/views2/1380778/page33/bg21.png)
30
4. Trouble Shooting
If the UPS system does not operate correctly, please solve the problem by using the table below.
Symptom
Possible cause
Remedy
No indication and alarm in the front
display panel even though the mains is
normal.
The AC input power is not
connected well.
Check if input cable firmly
connected to the mains.
The icon and the warning code
flash on LCD display and alarm
beeps every second.
EPO function is activated. At
this time, the EPO switch is in
“OFF” status or the jumper is
open.
Set the circuit in closed
position to disable the EPO
function.
The icon and flash on
LCD display and alarm beeps every
second.
The external or internal
battery is incorrectly
connected.
Check if all batteries are
connected well.
The icon and flash on
LCD display and alarm beeps twice
every second.
UPS is overload.
Remove excess loads from UPS
output.
UPS is overloaded. Devices
connected to the UPS are fed
directly by the electrical
network via the Bypass.
Remove excess loads from UPS
output.
After repetitive overloads, the
UPS is locked in the Bypass
mode. Connected devices are
fed directly by the mains.
Remove excess loads from UPS
output first. Then shut down
the UPS and restart it.
Fault code is shown as 43. The icon
lights on LCD display and
alarm beeps continuously.
UPS is overload too long and
becomes fault. Then UPS shut
down automatically.
Remove excess loads from UPS
output and restart it.
Fault code is shown as 14, the icon
lights on LCD display, and
alarm beeps continuously.
The UPS shut down
automatically because short
circuit occurs on the UPS
output.
Check output wiring and if
connected devices are in short
circuit status.
Other fault codes are shown on LCD
display and alarm beeps continuously.
A UPS internal fault has
occurred.
Contact your dealer
Battery backup time is shorter than
nominal value
Batteries are not fully charged
Charge the batteries for at
least 7 hours and then check
capacity. If the problem still
persists, consult your dealer.
Batteries defect
Contact your dealer to replace
the battery.
The icon and flash on LCD
display and alarm beeps every second.
Fan is locked or not working;
or the UPS temperature is too
high.
Check fans and notify dealer.
Содержание
- Table of contents p.3
- 1 transportation and storage p.4
- Safety and emc instructions p.4
- 3 installation p.4
- 2 preparation p.4
- Connection warnings p.5
- 6 standards p.6
- 5 operation p.6
- Installation and operation p.7
- 1 unpacking and inspection p.7
- 2 rear panel view p.8
- 3 single ups installation p.9
- 4 ups installation for parallel system p.11
- 5 software installation p.12
- 4 single ups operation p.15
- 3 audible alarm p.15
- 5 parallel operation p.18
- 6 abbreviation meaning in lcd display p.19
- 7 lcd setting p.20
- 8 operating mode status description p.25
- 10 warning indicator p.31
- 9 fault code p.31
- 11 warning code p.32
- Trouble shooting p.33
- Storage and maintenance p.35
- 2 maintenance p.35
- 1 storage p.35
- Specifications p.36
Похожие устройства
-
FSP Proline 3/3 30KИнструкция по эксплуатации -
FSP Proline 3/3 20KИнструкция по эксплуатации -
FSP Proline 3/3 15KИнструкция по эксплуатации -
FSP Proline 3/1 30KИнструкция по эксплуатации -
FSP Proline 3/1 20KИнструкция по эксплуатации -
FSP Proline 3/1 15KИнструкция по эксплуатации -
FSP Proline 3/1 10KИнструкция по эксплуатации -
FSP Knight PRO + RM 6KИнструкция по эксплуатации -
FSP Knight PRO + RM 10KИнструкция по эксплуатации -
FSP Knight PRO+ 1KИнструкция по эксплуатации -
FSP Knight PRO+ 2KИнструкция по эксплуатации -
FSP Knight PRO+ 3KИнструкция по эксплуатации
Узнайте, как устранить неполадки с источниками бесперебойного питания. Полезные советы по диагностике и устранению проблем с подключением и перегрузкой.