7.3 - Condensate drain connection
The condensate drain pan is supplied with 7/8" OD copper
tube outlet.
Ensure that water condensate will be properly drained out
from the drain pan which must be connected to the main
drain piping.
The drain line must be installed with a downward slope.
Ensure water trap is available on drain piping.
On completion, the drain line should be insulated.
Warning
All foreign material must be removed from the drain
pan.
Caution
Check that there is no counter-slope which would prevent
condensates from flowing.
B
AA
Trap for condensate evacuation
The height A must be equal to 2 times the value of the
negative pressure present in the condensate reception
zone (example : negative pressure = 40 mm, height A =
80 mm, height B = 160 mm).
7 - Water Connections (continued)
7.4 - Winterizing water coils
In winter, due to a general shutdown of the installation or
a failure of outdoor air damper control, coil freeze-up may
occur.
To avoid coil damage, it is recommended to drain
completely the non used coils or to fill them with an anti-
freeze solution.
The concentration of anti-freeze solution must be regularly
and carefully checked before each winter season.
It is highly advised to place a heating coil before a cooling
coil for an operation during winter season.
Caution
Carefully read instructions for mixing anti-freeze solution
used. Some products will have a higher freezing point in
its natural state than when mixed with water.
The freezing of coils is not the responsibility of the
manufacturer.