Airwell Wespak 5.05 [13/20] Electrical connections

Airwell Wespak 5.05 [13/20] Electrical connections
11
English
Dual-voltage motors with
Y / ∆ connections
Skeleton
diagrams
External connection diagrams
D.O.L. starting
Y / ∆ starting
- Voltage : U
- Connection : ∆ (at lower
marked voltage)
- E.G. : 230 V / ∆
- Voltage : U √3
- Connection : Y (at lower
marked voltage)
- E.G. : 400 V / Y
8.1 - Unit connection
Before undertaking any electrical connection, make sure
that the fan motor is suitable for electrical power supply.
All wiring must be done in accordance with applicable
electrical codes and regulations.
Earthing of unit is imperative.
The manufacturer or its representative will not be held
responsible for accidents caused by incorrect or non-existing
earthing.
The units are not supplied with electrical panel.
Wiring on the electric motors must be done at site. All
motors are designed and produced in accordance with the
standards in use.
The connection of these motors will be done according to the
indications affixed on the nameplate and on the diagram
located in the terminal box.
All motors are equipped, as standard, with a normally closed
internal overload protection sensor. This safety device shall
Caution
The electric heater must never operate without the
ventilation.
8 - Electrical connections
be imperatively connected to the control circuit of the motor.
The non-respect of this instruction will cancel compulsorily
the warranty on the motor.
Power supply cables entering into the unit, must be run
through cable glands mounted on unit panel.
All orifices for cable entry done on the panels must be sealed
to prevent leakage.
8.2 - Electric heater
The factory mounted electric heater is fitted with a manual
reset high temperature cut-out switch which de-energizes
the heater in case of fan motor failure.
For electrical connection, refer to wiring diagram sticked on
the unit.
W2
L1 L2 L3
U2 V2
U1 V1 W1
W2
L1 L2 L3
U2 V2
U1 V1 W1
W2
L1
L2L3
W1
V2 V1
U2
U1
Démarreur Y/
W2
L1 L2 L3
U2 V2
U1 V1 W1
W2
L1 L2 L3
U2 V2
U1 V1 W1
W2
L1
L2L3
W1
V2 V1
U2
U1
Démarreur Y/
W2
L1 L2 L3
U2 V2
U1 V1 W1
W2
L1 L2 L3
U2 V2
U1 V1 W1
W2
L1
L2L3
W1
V2 V1
U2
U1
Y/ Starter
W2
L1 L2 L3
U2 V2
U1 V1 W1
W2 V2
L1
L2L3
W1 V1
U2
U1
W2
L1 L2 L3
U2 V2
U1 V1 W1
W2 V2
L1
L2L3
W1 V1
U2
U1
(1) Diagrams valid for :
- 3-phase 230 ∆ / 400 Y V motors with power from 0.25 to 4.5 kW at 1500 rpm and from 0.25 to 5.5 kW at 3000 rpm,
- 3-phase 400 ∆V motors with power higher or equal to 5.5 kW at 1500 rpm, using Y / ∆ starter.
Single speed motors (1)