Summer performances Size : RT4D 20
Outdoor air percentage = 0% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb °C / Wet bulb °C)
25 30 32 35 38 40
24 °C / 18 °C
Cooling capacity (kW) 14.7 14.3 14.1 13.7 13.4 13.1
Compressors power input (kW) 3.3 3.7 3.8 4.1 4.3 4.5
26 °C / 19.5 °C
Cooling capacity (kW) 15.5 15 14.8 14.4 14 13.7
Compressors power input (kW) 3.4 3.7 3.9 4.1 4.4 4.5
29 °C / 22 °C
Cooling capacity (kW) 16.7 16.2 15.9 15.5 15.1 14.8
compressors power input (kW) 3.5 3.8 4 4.2 4.5 4.6
31 °C / 24 °C
Cooling capacity (kW) 17.7 17.1 16.8 16.4 16 15.7
Compressors power input (kW) 3.5 3.9 4.1 4.3 4.6 4.7
Winter performances Size : RT4D 20
Outdoor air percentage = 0% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb temp. °C / Relative humidity %)
-7 -3 0 3 7 10
16 °C / 40 %
Heating capacity (kW) 9.3 10.1 11 11.9 13.1 14.1
Compressors power input (kW) 3.1 3.2 3.4 3.6 3.8 4
18 °C / 40 %
Heating capacity (kW) 9.3 10.1 11 11.8 13.1 14
Compressors power input (kW) 3.2 3.4 3.5 3.7 4 4.2
20 °C / 40 %
Heating capacity (kW) 9.3 10.1 10.9 11.8 13 13.9
Compressors power input (kW) 3.3 3.5 3.7 3.9 4.1 4.4
22 °C / 40 %
Heating capacity (kW) 9.3 10.1 10.9 11.8 12.9 13.8
Compressors power input (kW) 3.5 3.6 3.8 4 4.3 4.5
Summer performances Size : RT4D 20
Outdoor air percentage = 25% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb °C / Wet bulb °C)
25 30 32 35 38 40
24 °C / 18 °C
Cooling capacity (kW) 15.9 15.5 15.3 14.8 14.5 14.2
Compressors power input (kW) 3.10 3.47 3.57 3.85 4.04 4.23
26 °C / 19.5 °C
Cooling capacity (kW) 16.8 16.2 16.0 15.6 15.2 14.8
Compressors power input (kW) 3.19 3.47 3.66 3.85 4.13 4.23
29 °C / 22 °C
Cooling capacity (kW) 18.1 17.5 17.2 16.8 16.4 16.0
Compressors power input (kW) 3.29 3.57 3.76 3.94 4.23 4.32
31 °C / 24 °C
Cooling capacity (kW) 19.2 18.5 18.2 17.8 17.3 17.0
Compressors power input (kW) 3.29 3.66 3.85 4.04 4.32 4.41
Winter performances Size : RT4D 20
Outdoor air percentage = 25% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb temp. °C / Relative humidity %)
-7 -3 0 3 7 10
16 °C / 40 %
Heating capacity (kW) 9.92 10.78 11.74 12.70 13.98 15.04
Compressors power input (kW) 2.60 2.68 2.85 3.02 3.19 3.36
18 °C / 40 %
Heating capacity (kW) 9.92 10.78 11.74 12.59 13.98 14.94
Compressors power input (kW) 2.68 2.85 2.94 3.10 3.36 3.52
20 °C / 40 %
Heating capacity (kW) 9.92 10.78 11.63 12.6 13.87 14.83
Compressors power input (kW) 2.77 2.94 3.10 3.27 3.44 3.69
22 °C / 40 %
Heating capacity (kW) 9.92 10.78 11.63 12.59 13.76 14.72
Compressors power input (kW) 2.94 3.02 3.19 3.36 3.61 3.78