Airwell RT4D 20 [21/56] Units performance data rt4d 140 continued

Airwell RT4D 20 [21/56] Units performance data rt4d 140 continued
Page 21
Summer performances Size : RT4D 140
Outdoor air percentage = 40% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb °C / Wet bulb °C)
25 30 32 35 38 40
24 °C / 18 °C
Cooling capacity (kW) 85.5 82.7 81.6 79.9 77.8 76.4
Compressors power input (kW) 15.44 17.33 18.18 19.51 20.83 21.78
26 °C / 19.5 °C
Cooling capacity (kW) 90.0 87.2 85.9 83.9 81.8 80.5
Compressors power input (kW) 15.63 17.52 18.37 19.7 21.12 22.06
29 °C / 22 °C
Cooling capacity (kW) 97.6 94.3 93.0 90.8 88.7 87.2
compressors power input (kW) 15.91 17.90 18.75 20.08 21.50 22.54
31 °C / 24 °C
Cooling capacity (kW) 103.7 100.3 98.8 96.6 94.2 92.6
Compressors power input (kW) 16.10 18.18 19.03 20.36 21.88 22.82
Winter performances Size : RT4D 140
Outdoor air percentage = 40% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb temp. °C / Relative humidity %)
-7 -3 0 3 7 10
16 °C / 40 %
Heating capacity (kW) 56.42 59.13 63.15 68.48 76.09 82.18
Compressors power input (kW) 13.28 13.46 13.73 14.17 14.80 15.33
18 °C / 40 %
Heating capacity (kW) 56.42 59.13 63.26 68.48 76.09 82.07
Compressors power input (kW) 13.81 14.08 14.44 14.88 15.51 16.04
20 °C / 40 %
Heating capacity (kW) 56.42 59.13 63.26 68.5 76.09 81.96
Compressors power input (kW) 14.53 14.71 15.06 15.5 16.22 16.84
22 °C / 40 %
Heating capacity (kW) 56.42 59.24 63.37 68.48 75.98 81.85
Compressors power input (kW) 15.15 15.42 15.69 16.31 17.02 17.56
Summer performances Size : RT4D 140
Outdoor air percentage = 60% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb °C / Wet bulb °C)
25 30 32 35 38 40
24 °C / 18 °C
Cooling capacity (kW) 90.9 88.0 86.8 84.9 82.8 81.2
Compressors power input (kW) 15.29 17.17 18.01 19.32 20.64 21.58
26 °C / 19.5 °C
Cooling capacity (kW) 95.7 92.7 91.4 89.2 87.0 85.5
Compressors power input (kW) 15.48 17.35 18.20 19.5 20.92 21.86
29 °C / 22 °C
Cooling capacity (kW) 103.8 100.3 98.9 96.6 94.3 92.7
Compressors power input (kW) 15.76 17.73 18.57 19.89 21.29 22.33
31 °C / 24 °C
Cooling capacity (kW) 110.2 106.6 105.0 102.7 100.2 98.5
Compressors power input (kW) 15.95 18.01 18.86 20.17 21.67 22.61
Winter performances Size : RT4D 140
Outdoor air percentage = 60% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb temp. °C / Relative humidity %)
-7 -3 0 3 7 10
16 °C / 40 %
Heating capacity (kW) 58.70 61.53 65.71 71.25 79.17 85.50
Compressors power input (kW) 12.60 12.76 13.02 13.44 14.03 14.54
18 °C / 40 %
Heating capacity (kW) 58.70 61.53 65.82 71.25 79.17 85.39
Compressors power input (kW) 13.10 13.36 13.69 14.12 14.71 15.22
20 °C / 40 %
Heating capacity (kW) 58.70 61.53 65.82 71.3 79.17 85.28
Compressors power input (kW) 13.78 13.95 14.29 14.7 15.38 15.98
22 °C / 40 %
Heating capacity (kW) 58.70 61.64 65.94 71.25 79.06 85.16
Compressors power input (kW) 14.37 14.62 14.88 15.47 16.15 16.65