Airwell RT4D 20 [11/56] Units performance data rt4d 20 continued

Airwell RT4D 20 [11/56] Units performance data rt4d 20 continued
Page 11
Summer performances Size : RT4D 20
Outdoor air percentage = 40% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb °C / Wet bulb °C)
25 30 32 35 38 40
24 °C / 18 °C
Cooling capacity (kW) 16.5 16.1 15.9 15.4 15.1 14.7
Compressors power input (kW) 3.10 3.47 3.57 3.85 4.04 4.23
26 °C / 19.5 °C
Cooling capacity (kW) 17.4 16.9 16.7 16.2 15.8 15.4
Compressors power input (kW) 3.19 3.47 3.66 3.85 4.13 4.23
29 °C / 22 °C
Cooling capacity (kW) 18.8 18.2 17.9 17.4 17.0 16.7
compressors power input (kW) 3.29 3.57 3.76 3.94 4.23 4.32
31 °C / 24 °C
Cooling capacity (kW) 19.9 19.2 18.9 18.5 18.0 17.7
Compressors power input (kW) 3.29 3.66 3.85 4.04 4.32 4.41
Winter performances Size : RT4D 20
Outdoor air percentage = 40% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb temp. °C / Relative humidity %)
-7 -3 0 3 7 10
16 °C / 40 %
Heating capacity (kW) 10.32 11.21 12.21 13.21 14.54 15.65
Compressors power input (kW) 2.50 2.58 2.75 2.91 3.07 3.23
18 °C / 40 %
Heating capacity (kW) 10.32 11.21 12.21 13.10 14.54 15.54
Compressors power input (kW) 2.58 2.75 2.83 2.99 3.23 3.39
20 °C / 40 %
Heating capacity (kW) 10.32 11.21 12.10 13.10 14.43 15.43
Compressors power input (kW) 2.67 2.83 2.99 3.15 3.31 3.55
22 °C / 40 %
Heating capacity (kW) 10.32 11.21 12.10 13.10 14.32 15.32
Compressors power input (kW) 2.83 2.91 3.07 3.23 3.47 3.63
Summer performances Size : RT4D 20
Outdoor air percentage = 60% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb °C / Wet bulb °C)
25 30 32 35 38 40
24 °C / 18 °C
Cooling capacity (kW) 17.6 17.1 16.8 16.4 16.0 15.6
Compressors power input (kW) 3.10 3.47 3.57 3.85 4.04 4.23
26 °C / 19.5 °C
Cooling capacity (kW) 18.5 17.9 17.7 17.2 16.7 16.4
Compressors power input (kW) 3.19 3.47 3.66 3.85 4.13 4.23
29 °C / 22 °C
Cooling capacity (kW) 19.9 19.3 19.0 18.5 18.0 17.7
Compressors power input (kW) 3.29 3.57 3.76 3.94 4.23 4.32
31 °C / 24 °C
Cooling capacity (kW) 21.1 20.4 20.1 19.6 19.1 18.7
Compressors power input (kW) 3.29 3.66 3.85 4.04 4.32 4.41
Winter performances Size : RT4D 20
Outdoor air percentage = 60% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb temp. °C / Relative humidity %)
-7 -3 0 3 7 10
16 °C / 40 %
Heating capacity (kW) 10.80 11.73 12.77 13.82 15.21 16.37
Compressors power input (kW) 2.42 2.50 2.65 2.81 2.96 3.12
18 °C / 40 %
Heating capacity (kW) 10.80 11.73 12.77 13.70 15.21 16.25
Compressors power input (kW) 2.50 2.65 2.73 2.89 3.12 3.28
20 °C / 40 %
Heating capacity (kW) 10.80 11.73 12.65 13.70 15.09 16.14
Compressors power input (kW) 2.57 2.73 2.89 3.04 3.20 3.43
22 °C / 40 %
Heating capacity (kW) 10.80 11.73 12.65 13.70 14.98 16.02
Compressors power input (kW) 2.73 2.81 2.96 3.12 3.35 3.51
Units Performance Data - RT4D 20 (continued)