Commissioning
5.3 Performance Check
Check as follows:
h
The inlet temperature of the fluid circulating in the
manifold of the exchangers.
h
The outlet temperature of the fluid circulating in
the manifold of the exchangers.
h
The flow rate of the fluid through the exchangers.
h
The current absorbed by compressors and fans at
the start-up and under steady operating condi-
tions.
Check the saturated evaporation and condensation
temperatures during the unit operation by connect-
ing the manometers with the two Schraeder valves
which can be found on the low and high pressure
side of refrigerating circuits.
5.4 Delivery to the User
h
Inform the user about the instructions for use
which can be found in Chapter 6.
High
pressure side
Low pressure
side
15-18°C above the air inlet temperature in
the battery.
5-7°C below the outlet temperature of the
water circulating from the evaporator.