AQL/AQH Control ERRATA CORRIGE
DIP OFF ON STANDARD
1 Pump ON only if the unit is ON Pump always ON OFF
2 Step ventilation Continuous ventilation OFF
3 Pump Off in antifreeze protection Pump On in antifreeze protection ON
4 Discharge of comp. 1 Discharge of comp. 2 OFF
5 Normal Slave OFF
6 Room temperature compensation No compensation ON
7 Enable input 5 pump’ thermal switch Disable input 5 pack unit = OFF
non pack = ON
8 Forced defrosting OFF Forced defrosting ON OFF
9 Serial address OFF
10 Serial address OFF
11 Serial address OFF
12 Serial address OFF
Display keys
Display menus
Display keys
Display menus
cool
6.2 Dip Switches
The control is provided with 2 DIP switch blocks:
DSW1 (12 dips) and DSW2 (8 dips).
FUNCTION OF DSW1 DIPS
h
Display keys
All th information is displayed on 4 displays (7-seg-
ments).
Use the > and ^ keys to enter the display menus as
follows: