Installation
4.6 Accumulation Tank Kit
The accumulation tank which has been designed for
mounting on AQL/AQH units is complete with all
the hydraulic and electrical components required
for the correct operation of the system.
These systems are carefully assembled and tested at
works. They are ready for operation after having
correctly realised all electrical and hydraulic con-
nections.
4.6.1 Features
20/35 units have one single tank whereas the units
starting from 40/50 have two tanks complete with
a standard connection. The kit will include an an-
tifreeze resistance, a drain cock, an automatic fill-
ing unit and an automatic air vent.
No pump is arranged on the kit since it is assumed
that the kit is meant for the units with a hydro option
where a pump and an expansion tank are already
available.
A tank arranged for mounting a heating booster re-
sistance kit may be optionally required (5 traps for
the kits from 20 to 50 and 8 traps for the kits for
larger sizes).
The tank is completely insulated with 30 Kg/m
3
closed cell polyethylene in a silver colour and en-
closed by a bearing structure made of passivated
and painted plates. The box is equipped with bulk-
heads which can be easily opened for internal in-
spection.
The kit is installed beneath the chiller. It is an inte-
gral part of the unit without changing the support
area.
Spring shock absorbers are also available for the
units starting from 40.
4.6.2 Supplied Material
The kits will be supplied with pipelines ready for in-
stallation. An antifreeze resistance with wiring, an
automatic water filling valve, a 3 bar safety valve,
a drain cock and a vent valve have already been
assembled.
Everything is placed on wooden pallets with wood-
en joists arranged on the kit for piling up and a film
for protection against atmospheric agents.
4.6.3 Operating Limits
The unit will guarantee the operation at an air tem-
perature of –10°C in a standard configuration with
one single antifreeze resistance.
4.6.4 Shock Absorbers
Shock absorbers are supplied for 20-35 sizes as a
standard. They shall be assembled by the customer
for 40-130 sizes during the installation.
IMPORTANT
Select the shock absorbers for the units with a hy-
dro kit.
4.6.5 Antifreeze Resistance
The antifreeze resistance of the tank (TEH) shall be
wired with the panel as it is shown by the diagram
attached to the unit.
4.6.6 Water Filter
The kit will use the water filter of the unit.
CAUTIONS
The unit + tank system shall be equipped with a fil-
ter for the 20-35 units. Use the filter + union as it is
shown by Figure 3.
Figure 3
Water filter
position
Positioning rubber shock absorbers
Figure 4
Positioning rubber
shock absorbers
Positioning rubber shock absorbers
Machines from 40 to 130