Trouble Shooting
8 TROUBLE SHOOTING
The following table will give a detailed list of unit faults and remedies. Contact an Authorised Itelco-Clima
Service Centre for any other problem which can not be clearly ascribed to one of the cases listed in the table
and/or for any other need for technical assistance.
Fault
The unit operates continuous-
ly, but without cooling.
Hoar-frost is building on the
suction line.
The noise level is too high.
The compressor oil level has
decreased.
One or two compressors are
not working.
Low refrigerant charge.
The dryer filter is clogged.
Loss of efficiency in one or both circuits.
The thermal expansion valve is out of calibra-
tion.
Vibrating pipelines.
The thermal expansion valve is whistling.
Noisy compressor.
One or more than one oil or gas leaks from
the circuit.
The compressor is mechanically damaged.
Faulty oil heater.
Power supply interruption.
The high pressure switch has tripped.
The control circuit fuse has tripped.
Loose terminals.
The thermal switches intended to protect the
power supply have tripped.
Wrong electrical connections.
The line voltage is too low.
The compressor motor has short-circuited.
The compressor has seized.
Check the fuses of the control circuit and make sure the circuit
is neither grounded nor short-circuited. Replace the fuses, if
required.
Tighten the terminals.
Make sure the safety and control devices are properly work-
ing. Identify and eliminate what has caused the trip.
Check the electrical connections of the control and safety de-
vices.
Check the line voltage. Remove the problem if it is due to the
plant. Contact the power supply company if it is due to the
network.
Check the continuity of the motor windings.
Replace the compressor.
Top up the refrigerant charge.
Replace the dryer filter.
Check the compressor and replace it, if required.
Increase overheating.
Check the charge.
Secure the pipelines.
Check the anchorage of the pipelines.
Top up the charge.
Check the dryer filter and replace it, if required.
Check the state of the valves.
The bearings have seized: replace the compressor.
Make sure that the nuts intended to anchor the compressor
have been firmly tightened.
Identify and eliminate all leaks.
Contact an Itelco-Clima Authorised Service Centre.
Make sure the electrical circuit and the elements of the electri-
cal heater are properly working. Replace any defective com-
ponent.
Check the fuses of the supply circuit and make sure the circuit
is neither grounded nor short-circuited.
Reset the pressure switch from the panel and restart the unit.
Identify and eliminate what has caused the high pressure
switch to trip.
Probable Cause Remedy