Airedale Ultima FreeCool UFC 575 [22/46] Chillers ultima freecool

Airedale Ultima FreeCool UFC 225 [22/46] Chillers ultima freecool
Chillers ULTIMA FREECOOL
Chillers
Installation & Maintenance Manual : 903-125 IM E 05/04/A
21
Installation Data
ELECTRICAL DATA
Model UFC350D-10 UFC400D-10 UFC450D-12 UFC500D-12 UFC575D-14
Unit Data (1)
Nominal Run Amps (2) A 212 236 275 308 347
Maximum Start Amps A 432 456 531 564 643
Permanent Supply VAC 230V 1PH 50Hz
Mains Supply VAC 400V 3PH 50Hz
Rec Permanent Fuse Size A 16 16 16 16 16
Rec Mains Fuse Size A 315 355 400 400 450
Max Permanent Incoming Cable
Size
mm² 4mm² Terminal
Max Mains Incoming Cable Size mm² Direct to Bus Bar
Control Circuit VAC 24V / 230VAC
Evaporator
Trace Heater Rating W 250 250 250 250 250
External Trace Heating
Available (fitted by others) W 500 500 500 500 500
Condenser Fan - Per Fan
Full Load Amps A 2.60 2.60 2.60 2.60 2.60
Locked Rotor Amps A 15.00 15.00 15.00 15.00 15.00
Motor Rating kW 1.70 1.70 1.70 1.70 1.70
Compressor - Per Compressor
Motor Rating kW 62 + 48 62 + 62 81 + 62 81 + 81 109 + 81
Nominal Run Amps (2) A 105 + 81 105 + 105 138 + 105 138 + 138 173 + 138
Crankcase Heater Rating W 150 150 150 150 150
Start Amps (3) 325 + 234 325 + 325 394 + 325 394 + 394 469 + 394
Type Of Start Star / Delta
QUIET DQ UFC350DQ-12 UFC400DQ-12 UFC450DQ-14 UFC500DQ-14 UFC575DQ-16
All data as above except:
Condenser Fan - Per Fan
Full Load Amps A 1.75 1.75 1.75 1.75 1.75
Locked Rotor Amps A 6.20 6.20 6.20 6.20 6.20
Motor Rating kW 0.98 0.98 0.98 0.98 0.98
SUPER QUIET DSQ UFC350DSQ-14 UFC400DSQ-14 UFC450DSQ-16 UFC500DSQ-16 UFC575DSQ-18
All data as above except:
Condenser Fan - Per Fan
Full Load Amps A 1.15 1.15 1.15 1.15 1.15
Locked Rotor Amps A 2.10 2.10 2.10 2.10 2.10
Motor Rating kW 0.70 0.70 0.70 0.70 0.70
OPTIONAL EXTRAS - Fitted to standard D models - for data on DQ & DSQ please refer to Airedale.
Power Factor Correction
Nominal Run Amps (2) A 192 214 249 278 314
Maximum Start Amps (3) A 432 456 531 564 643
Recommended Mains
Fuse
A 315 315 355 400 400
Compressor Nominal
Run Amps - Per
Compressor
A 94 + 72 94 + 94 123 + 94 123 + 123 155 + 123
Closed Transition
Nominal Run Amps (2) A 212 236 275 308 347
Maximum Start Amps A 432 456 531 564 643
Recommended Mains
Fuse
A 315 355 400 400 450
Compressor Nominal
Run Amps - Per
Compressor
A 105 + 81 105 + 105 138 + 105 138 + 138 173 + 138
(1) Refers to standard speed fans.
(2) Based at 12/7°C water and 30°C ambient
(3) Starting amps refers to the Star connection only.

Содержание