Airedale Ultima FreeCool UFC 575 [35/46] Ultima freecool chillers

Airedale Ultima FreeCool UFC 225 [35/46] Ultima freecool chillers
ULTIMA FREECOOL Chillers
Chillers
34
Installation & Maintenance Manual : 903-125 IM E 05/04/A
Commissioning Procedure
PRE COMMISSIONING CHECKLIST (CONT..)
Waterflow
Commissioning
Drive the 3-way valve fully open by raising the return water temperature above the
ambient and measure the pressure drop across the free cooling coils.
Lower the return water temperature to below the ambient to close the valve fully.
Adjust the bypass DRV to achieve equivalent pressure drop as across the coils.
Recheck again during valve fully open and closed checking pressure drop across
the unit to ensure equal pressure drops are achieved.
Reduce the flow rate to 75% of design and ensure that the evaporator flow switch
trips at this flow rate, adjust as necessary.
Ensure this alarm is recognised as “Water Flow Fail” at the display and
disengages the circuits operation immediately. Restore flow rate to the design and
check the alarm has self-cleared.
To switch the unit OFF, use the microprocessor keypad as follows:
Press
Prg
, press , press , press & finally .
RECORD
Fully open all liquid line and discharge service ball valves on each circuit.
Re-instate both the liquid injection and liquid line solenoid valves.
CAUTION
Remove the link from the MCCB for the auxiliary alarm contact.