Installation & Maintenance Manual : 903-125 IM E 05/04/A
13
Installation Data
1 Locate and secure mount using bolting down holes provided in base plate.
2 Ensure mounts are located in line with the chiller base.
3 If applicable remove compressor enclosure covers to allow access to AV fixing
points on the chiller base.
4 Position the machine using the centrally located stud, which allows the machine to
be bolted down securely.
5 Loosen transit bolts and turn nut 3 clockwise until top plate 6 lifts clear of support
posts. Tighten lock nut 4 when machine is at desired height and level.
ANTI VIBRATION
MOUNTING
CLS Type (Optional)
6 Adjust and lock nuts on transit bolts such that a small (3-5mm) gap is left between
washer and grommet. Refer diagram below.
Mountings must be adjusted incrementally in turn. Do not adjust 1 mount at a time
as this may overload and damage springs.
CAUTION
Do not connect any services until all anti vibration mounts have been
fully adjusted.
20 20
20
20
100
14 Ø
BASE PLATE
TOP PLATE
100
200
ELEVATION
1
2
3
4
5
6
7
8
9
10
11
1
2
13
13
5
M16 STUD
M16 STUD
180-210
= =
==
COMPONENTS
1 High deflection steel spring
2 Spring pressure plate
3 Height adjusting nut
4 Locking nut
5 Load bearing supports
6 Load bearing top plate
7 High frequency isolation pad
8 10 dia holding down bolt holes
9 High frequency isolation grommets
10 Steel spring location rings
11 Transportation/restraining bolts
12 Machine frame
13 Machine holding stud/nuts