Installation & Maintenance Manual : 903-125 IM E 05/04/A
7
General Description
STANDARD FEATURES
Each refrigeration circuit is supplied with the following:
Full operating charge of R407C
Liquid injection oil cooling circuit fitted to each compressor as standard with filter,
sight glass, strainer and non-return valve
Electronic expansion valve
Liquid line ball valve
Discharge line ball valve
Discharge line mufflers (DSQ MODELS ONLY)
Large capacity filter drier with replaceable cores
Liquid line sight glass
Low pressure switch with manual reset via microprocessor controller
High pressure switch with manual reset
Suction and liquid pressure transducers
Dual Pressure relief valve with integral rupture disc and indicator gauge offering
easy maintenance complying with Pressure Regulations
Refrigeration
Valves for refrigeration head pressure control in simultaneous Free Cooling and
Mechanical cooling mode
Each water glycol circuit is supplied with the following:
Water Flow switch
3 way modulating valve to control free-cooling operation
Strategically placed automatic air vents
Strategically placed drain valves
Butterfly shut off valves for Free-cooling coil isolation to allow for maintenance
Pressure transducers across evaporator to monitor water pressure drop
Water / Glycol
Inlet water filter 1/16” mesh
Controls
microprocessor controlled providing 6-8 stages of mechanical cooling
(Depending on model size), modulating condenser fans and valve to offer 0-100% free-
cooling when ambients permit. The controller incorporates full Building Management
System capabilities, full details can be found in the
Controls section.
Weatherproof electrical power and control panels are situated at the end of the unit
and contain:
Individual mains power compartments for each refrigeration circuit
Separate door locking electrical isolation for each mains compartment
Dedicated control panel and isolator for fans and integral pumps (when fitted)
Electrical
Emergency Stop fitted to controls compartment door
CAUTION
The Emergency Stop MUST NOT be used to stop the chiller other than in the event
of an emergency.
Separate, fully accessible, controls compartment, allowing safe adjustment of
microprocessor set points whilst the unit is operational
Dedicated bus-bar chamber for connection of incoming 3-phase and earth mains
power supply
Circuit breakers for protection of all major unit components
Phase Rotation Relay also incorporating loss of phase protection
The electrical power and control panel is wired to the latest European standards and
codes of practice
Mains supply is 3 phase and a neutral is not required.