Airedale Ultima FreeCool UFC 650 [21/46] Ultima freecool chillers
![Airedale Ultima FreeCool UFC 575 [21/46] Ultima freecool chillers](/views2/1409517/page21/bg15.png)
ULTIMA FREECOOL Chillers
Chillers
20
Installation & Maintenance Manual : 903-125 IM E 05/04/A
Installation Data
ELECTRICAL DATA
Model UFC200D-8 UFC225D-8 UFC250D-8 UFC275D-8 UFC300D-8
Unit Data (1)
Nominal Run Amps (2) A 141 154 167 174 183
Maximum Start Amps A 289 335 348 356 336
Permanent Supply VAC 230V 1PH 50Hz
Mains Supply VAC 400V 3PH 50Hz
Rec Permanent Fuse Size A 16 16 16 16 16
Rec Mains Fuse Size A 200 200 250 250 250
Max Permanent Incoming Cable
Size
mm² 4mm² Terminal
Max Mains Incoming Cable Size mm² Direct to Bus Bar
Control Circuit VAC 24V / 230VAC
Evaporator
Trace Heater Rating W 200 200 200 200 250
External Trace Heating
Available (fitted by others) W 500 500 500 500 500
Condenser Fan - Per Fan
Full Load Amps A 2.60 2.60 2.60 2.60 2.60
Locked Rotor Amps A 15.00 15.00 15.00 15.00 15.00
Motor Rating kW 1.70 1.70 1.70 1.70 1.70
Compressor - Per Compressor
Motor Rating kW 33 + 33 41 + 33 41 + 41 48 + 41 48 + 48
Nominal Run Amps (2) A 60 + 60 73 + 60 73 + 73 81 + 73 81 + 81
Crankcase Heater Rating W 150 150 150 150 150
Start Amps (3) 208 + 208 254 + 208 254 + 254 234 + 254 234 + 234
Type Of Start Star / Delta
QUIET DQ UFC200DQ-8 UFC225DQ-8 UFC250DQ-8 UFC275DQ-8 UFC300DQ-10
All data as above except:
Condenser Fan - Per Fan
Full Load Amps A 1.75 1.75 1.75 1.75 1.75
Locked Rotor Amps A 6.20 6.20 6.20 6.20 6.20
Motor Rating kW 0.98 0.98 0.98 0.98 0.98
SUPER QUIET DSQ UFC200DSQ-8 UFC225DSQ-8 UFC250DSQ-8 UFC275DSQ-10 UFC300DSQ-10
All data as above except:
Condenser Fan - Per Fan
Full Load Amps A 1.15 1.15 1.15 1.15 1.15
Locked Rotor Amps A 2.10 2.10 2.10 2.10 2.10
Motor Rating kW 0.70 0.70 0.70 0.70 0.70
OPTIONAL EXTRAS - Fitted to standard D models - for data on DQ & DSQ please refer to Airedale.
Power Factor Correction
Nominal Run Amps (2) A 129 140 151 158 165
Maximum Start Amps (3) A 289 335 348 356 336
Recommended Mains
Fuse
A 160 200 200 250 250
Compressor Nominal
Run Amps - Per
Compressor
A 54 + 54 65 + 54 65 + 65 72 + 65 72 + 72
Closed Transition
Nominal Run Amps (2) A 141 154 167 174 183
Maximum Start Amps A 289 335 348 356 336
Recommended Mains
Fuse
A 200 200 250 250 250
Compressor Nominal
Run Amps - Per
Compressor
A 60 + 60 73 + 60 73 + 73 81 + 73 81 + 81
(1) Refers to standard speed fans.
(2) Based at 12/7°C water and 30°C ambient
(3) Starting amps refers to the Star connection only.
Содержание
- Free cooling chiller 200 750 kw 1
- Installation operating maintenance manual 1
- Ultima freecool 1
- About airedale products customer services 2
- Caution 2
- Chillers 2
- Customer services 2
- Spares 2
- Training 2
- Ultima freecool chillers 2
- Warranty commissioning maintenance 2
- Chillers ultima freecool 3
- Contents 3
- Caution 4
- Chillers 4
- General statement 4
- Important 4
- Safety 4
- Ultima freecool chillers 4
- Chillers 5
- Chillers ultima freecool 5
- Exclusions 5
- General 5
- Procedure 5
- Returns analysis 5
- Warranty 5
- Warranty is only valid in the event that 5
- Ce directive 6
- Chillers 6
- Free cooling chiller 6
- General description 6
- Introduction 6
- Quiet chiller dq 6
- Refrigerants 6
- Standard chiller d 6
- Standard features 6
- Super quiet chiller dsq 6
- Ultima freecool chillers 6
- Unit identification 6
- Caution 7
- Chillers 7
- Chillers ultima freecool 7
- Controls 7
- Electrical 7
- General description 7
- Refrigeration 7
- Standard features 7
- Water glycol 7
- Chillers 8
- Closed transition star delta compressor start 8
- Factory fitted 8
- General description 8
- Loose item 8
- Optional extras energy saving 8
- Optional extras general 8
- Optional unit cover 8
- Power factor correction 8
- Ultima freecool chillers 8
- Chillers 9
- Chillers ultima freecool 9
- Dimensions 9
- Installation data 9
- Caution 10
- Chillers 10
- Dimensions cont 10
- Installation data 10
- Point loading centre of gravity 10
- Ultima freecool chillers 10
- Chillers 11
- Chillers ultima freecool 11
- Installation data 11
- Weights 11
- 18 fans 12
- Caution 12
- Chillers 12
- Installation data 12
- Lifting dimensions 12
- Ultima freecool chillers 12
- Unit lifting 12
- Airedale international air conditioning ltd 13
- Anti vibration mount spring type specification installation instructions 13
- Caution 13
- Change 13
- Components 13
- Date 18 10 05 13
- Dimensions 13
- E mail info airedale com website www airedale com 13
- Installation 13
- Leeds road rawdon leeds ls19 6jy england tel 44 0 113 239 1000 fax 44 0 113 250 7219 13
- Manual affected technical installation 13
- Manual part no 901 108 tm e 02 05 a 13
- Technical update 13
- Ultima ucc uccu 30 450 ultima ucc uccu 30 450 ucfc urac uwc75 450 ufc usc200 750 13
- Anti vibration mounting 14
- Caution 14
- Chillers 14
- Chillers ultima freecool 14
- Installation data 14
- Caution 15
- Chillers 15
- Installation data 15
- Positioning 15
- Ultima freecool chillers 15
- Caution 16
- Chillers 16
- Chillers ultima freecool 16
- Installation data 16
- Pump statement 16
- Recommended minimum component requirements 16
- Standard recommended installation 16
- Water system data 16
- Caution 17
- Chillers 17
- Filling 17
- Installation data 17
- Pressure testing 17
- Ultima freecool chillers 17
- Water system data 17
- Caution 18
- Chillers 18
- Chillers ultima freecool 18
- Ethylene glycol nominal correction factors 18
- Glycol data caution 18
- Installation data 18
- Propylene glycol nominal correction factors 18
- Caution 19
- Chillers 19
- Electrical data 19
- General 19
- Installation data 19
- Interlocks protection 19
- Ultima freecool chillers 19
- Caution 20
- Chillers 20
- Chillers ultima freecool 20
- Installation data 20
- Interconnecting wiring 20
- No pumps 20
- With pumps 20
- Chillers 21
- Electrical data 21
- Installation data 21
- Ultima freecool chillers 21
- Chillers 22
- Chillers ultima freecool 22
- Electrical data 22
- Installation data 22
- Chillers 23
- Electrical data 23
- Installation data 23
- Ultima freecool chillers 23
- Caution 24
- Chillers 24
- Chillers ultima freecool 24
- Constant supply temperature control 24
- Control scheme features 24
- Controls 24
- Free cooling operation 24
- Variable supply temperature control 24
- Chillers 25
- Controls 25
- General 25
- Navigation 25
- Operation 25
- Standard keypad display 25
- Standard operating page 25
- Ultima freecool chillers 25
- Chillers 26
- Chillers ultima freecool 26
- Controls 26
- Menus listed in sequence 26
- Operation cont standard operating page cont 26
- Password protection 26
- Real time clock 26
- Setting up unit on off 26
- Technical support 26
- Time zones 26
- Analogue outputs 27
- Chillers 27
- Controls 27
- Digital inputs analogue inputs 27
- Digital outputs 27
- Ultima freecool chillers 27
- Viewing unit operating status status menu 27
- Alarm handling 28
- Alarms 28
- Chillers 28
- Chillers ultima freecool 28
- Circuit isolator 28
- Common alarms 28
- Compressor overload 28
- Controls 28
- Electronic expansion valve failure 28
- Emergency stop 28
- Evaporator flow failure 28
- High discharge 28
- High liquid pressure 28
- Individual circuit alarms 28
- Low suction pressure 28
- Low supply temperature 28
- Phase rotation 28
- Chillers 29
- Commissioning data 29
- General data operating limits 29
- Mechanical data oil refrigerant charges 29
- Ultima freecool chillers 29
- Chillers 30
- Chillers ultima freecool 30
- Commissioning data 30
- Quiet dq models 30
- Standard d models 30
- Waterside pressure drops 30
- Chillers 31
- Commissioning data 31
- Super quiet dsq models 31
- Ultima freecool chillers 31
- Waterside pressure drops 31
- Caution 32
- Checks at compressor start up 32
- Chillers 32
- Chillers ultima freecool 32
- Clients incoming supply 400 3 50 32
- Commissioning data 32
- Crankcase heater 32
- Electrical data compressor start up information 32
- Operational sequence 32
- Pre start up check 32
- Refrigerant charge 32
- Starting sequence star delta starting 32
- Commissioning data 33
- Ultima freecool chillers 33
- Caution 34
- Chillers 34
- Chillers ultima freecool 34
- Commissioning procedure 34
- General 34
- Pre commissioning checklist 34
- Record 34
- Caution 35
- Chillers 35
- Commissioning procedure 35
- Pre commissioning checklist cont waterflow commissioning 35
- Record 35
- Ultima freecool chillers 35
- Caution 36
- Chillers 36
- Chillers ultima freecool 36
- Commissioning checklist 36
- Commissioning procedure 36
- Record 36
- Caution 37
- Chillers 37
- General maintenance 37
- Maintenance 37
- Ultima freecool chillers 37
- Chillers 38
- Chillers ultima freecool 38
- Compressor maintenance 38
- Electronic expansion valve option 38
- General maintenance 38
- Maintenance 38
- Shut down periods 38
- Chillers 39
- Maintenance 39
- Ultima freecool chillers 39
- Unit schematic 39
- Chillers 40
- Chillers ultima freecool 40
- Chillers 41
- Parts identification 41
- Spares 41
- Ultima freecool chillers 41
- Chillers 42
- Chillers ultima freecool 42
- Parts identification 42
- Chillers 44
- Chillers ultima freecool 44
- Head office 45
- International sales offices 45
- Regional sales offices 45
- Airedale departmental contact details 46
- Customer services 46
Похожие устройства
- Airedale Ultima FreeCool UFC 700 Инструкция по эксплуатации
- Airedale Ultima FreeCool UFC 750 Инструкция по эксплуатации
- Airedale UWC 75 Инструкция по эксплуатации
- Airedale UWC 100 Инструкция по эксплуатации
- Airedale UWC 125 Инструкция по эксплуатации
- Airedale UWC 150 Инструкция по эксплуатации
- Airedale UWC 225 Инструкция по эксплуатации
- Airedale UWC 300 Инструкция по эксплуатации
- Airedale UWC 400 Инструкция по эксплуатации
- Airedale UWC 475 Инструкция по эксплуатации
- Acson AWM07F Инструкция по эксплуатации
- Acson AWM10F Инструкция по эксплуатации
- Acson AWM07FR Инструкция по эксплуатации
- Acson ALC07B Инструкция по эксплуатации
- Acson ALC10B Инструкция по эксплуатации
- Acson ALC07BR Инструкция по эксплуатации
- Acson ALC10BR Инструкция по эксплуатации
- Acson AWM15F Инструкция по эксплуатации
- Acson AWM20F Инструкция по эксплуатации
- Acson AWM25F Инструкция по эксплуатации