Ecoflam MAX GAS 500 MD ТL - MB-DLE 410 350/500 [16/76] Connection to the gas pipeline

Ecoflam MAX GAS 500 MD ТL - MB-DLE 410 350/500 [16/76] Connection to the gas pipeline
2
1
+
MOUNTING TO THE BOILER
ELECTRICAL CONNECTIONS
All burners factory tested at 230V 50 Hz monophase (Max Gas 350) or 400 V 50 Hz three-phase (Max Gas 500) for
motors and 230V 50 Hz monophase for auxiliary equipment. If mains supply is 230 V 50 Hz threephase withuot neu-
tral, change position of connectors on burner as in fig. Protect burner supply line with safety fuses and any other devi-
ces required by safety standards obtaining in the country in question.
CONNECTION TO THE GAS PIPELINE
Once connected the burner to the gas pipeline, it is necessary to control that this last is perfectly sealed. Also verify that
the chimney is not obstructed. Open the gas cock and carefully bleed the piping through the pressure gauge connector,
then check the pressure value trough a suitable gauge. Power on the system and adjust the thermostats to the desired
temperature. When thermostats close, the sealing control device runs a seal test of valves; at the end of the test the bur-
ner will be enabled to run the start-up sequence.
MODEL A B C D D1 E F G I L M N O
MAX GAS 350 485 277 208 175 335 466 157 280 185/200 185/200 M8 62 101
MAX GAS 500 485 277 208 175 335 466 157 280 185/200 185/200 M8 62 101
D = SHORT HEAD D1= LONG HEAD
OVERALL DIMENSIONS
571664
?
157
280 114
C
I
B
A
L
581
002
185
200
N
E
D-D1
O
G
F
M
EN
420010318203 Max Gas 350 - 500 P/P AB
16