Ecoflam MAX GAS 500 MD ТL - MB-DLE 410 350/500 [18/76] Control boxes lme21 lme22

Ecoflam MAX GAS 350 PAB ТL - MB-DLE 410 350/500 [18/76] Control boxes lme21 lme22
Color code table for multicolor signal lamp (LED)
Status Color code Color
Waiting time «tw», other waiting states ................................................................................... Off
Ignition phase, ignition controlled ● ❍ ● ❍ ● ❍ ● ❍ ● ❍ ● ❍ ● ❍ ● ❍ ● ❍ ● ❍ ● ❍ Flashing yellow
Operation, flame o.k. ................................................................................... Green
Operation, flame not o.k. ❑ ❍ ❑ ❍ ❑ ❍ ❑ ❍ ❑ ❍ ❑ ❍ ❑ ❍ ❑ ❍ ❑ ❍ ❑ ❍ ❑ ❍ Flashing green
Extraneous light on burner startup ❑ ▲ ❑ ▲ ❑ ▲ ❑ ▲ ❑ ▲ ❑ ▲ ❑ ▲ ❑ ▲ ❑ ▲ ❑ ▲ ❑ ▲ Green-red
Undervoltage ● ▲ ● ▲ ● ▲ ● ▲ ● ▲ ● ▲ ● ▲ ● ▲ ● ▲ ● ▲ ● ▲ Yellow-red
Fault, alarm ................................................................................... Red
Error code output (refer to «Error code
table») ▲ ❍ ▲ ❍ ▲ ❍ ▲ ❍ ▲ ❍ ▲ ❍ ▲ ❍ ▲ ❍ Flashing red
Interface diagnostics ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲ Red flicker light
Legend: ....... Steady on Red Green Off Yellow
Connection diagram and control sequence of LME21
RESET
M
V1
V2
Z
AL
T
T
R / W
GP
STB
7101a22e/0609
LP
EK2
K1
K2/1
K3
K4K2/2
H
Si
N
SB / R
W / GP
AL
LP
V1
(LR) V2
Z
FS
tw
t1
t3n
TSA
t4
7101d05/0409
ABB´C
D
t3
t10
M
AGK25... PTC resistor
AL Error message (alarm)
V... Fuel valve
CPI Closed Position Indicator
DBR... Wire link
EK Lockout reset button (internal)
EK2 Remote lockout reset button
ION Ionization probe
FS Flame signal
FSV Flame signal amplifier
GP Pressure switch
H Main switch
HS Auxiliary contactor, relay
K1...4 Internal relays
KL Low-fire
LK Air damper
LKP Air damper position
LP Air pressure switch
LR Load controller
M Fan motor
R Control thermostat / pressurestat
SA Actuator
STB Safety limit thermostat
Si External pre-fuse
t Time
W Limit thermostat / pressure
switch
Z Ignition transformer
ZV Pilot gas valve
A Start command (switching on
by «R»)
B-B´ Interval for establishment of
flame
C Operating position of burner
reached
C-D Burner operation (generation
of heat)
D Controlled shutdown by «R»
t1 Prepurge time
t3 Preignition time
t3n Postignition time
t4 Interval between ignition
«Off» and release of «V2»
t10 Specified time for air pressure
signal
t11 Programmed opening time for
actuator «SA»
t12 Programmed closing time for
actuator «SA»
TSA Ignition safety time
tw Waiting time
CONTROL BOXES LME21-LME22
Connection diagram and control sequence LME22… / LME23…
NT
μ
C control
RESET
EK
FSV
ION
1
2
3
M
4
BV1
5
BV2
7
Z
10
AL
T
12
R / W
GP
STB
9
7101a02e/0606
p
a
6
LP
8
EK
11
K1
K2/1
K3
K4
K2/2
H
Si
SA
L
N
QRC
br
bl
sw
12
12
Nur LME23...
SB / R
W / GP
AL
LP
SA
BV1
(LR) BV2
Z
FS
tw
t1
t3n
TSA
t4
7101d02/0606
t11
t12
EK2
12
10
3
7
4
5
6
1
8
A
B
C
D
9
t3
t10
LK
M
I
11
EN
420010318203 Max Gas 350 - 500 P/P AB
18