FIRING HEAD AND AIR SETTING
To adjust air flow, turn the screw A as required. To reduce output, turn screw clockwise, to increase it turn screw coun-
terclockwise. Note: screw B not used.
Error code table
Red blink code of «AL» at Possible cause
signal lamp (LED)) term. 10
2 blinks on No establishment of flame at the end of «TSA»
- Faulty or soiled fuel valves - Faulty or soiled flame detector
- Poor adjustment of burner, no fuel - Faulty ignition equipment
3 blinks on «LP» faulty
- Loss of air pressure signal after «t10», - «LP» welded in normal position
4 blinks on Extraneous light when burner is started up
5 blinks on Time out «LP»
- «LP» welded in working position
6 blinks on Free
7 blinks on Too many losses of flame during operation
(limitation of the number of repetitions)- Faulty or soiled fuel valves.
- Faulty or soiled flame detector - Poor adjustment of burner.
8 blinks on Free
9 blinks on Free
10 blinks off Wiring error or internal error, output contacts, other faults.
14 blinks on CPI contact not closed