Ecoflam MAX GAS 350 P TW ТC - VCS-125 350/500 [23/76] Flame detection system check

Ecoflam MAX GAS 350 P TW ТC - VCS-125 350/500 [23/76] Flame detection system check
A
A
2,5
3
POSITION OF ELECTRODES
IONIZATION
PROBE
IGNITION
ELECTRODE
With the burner switched off, connect a DC microammeter with a 0÷50 or 0÷100 µA dial. When the burner is run-
ning, and is properly adjusted, the value read must be steady and never be smaller than 1,5 µA (LME 11/21/22) .
LANDIS
LME11/LME21-22
min. 1,5 µA
1
FLAME DETECTION SYSTEM CHECK
REMOVING FIRING HEAD