REM OVING TH E BLAST TUBE
N O ZZLE CLEANING AN D REPLACEM EN T
Use only the suitable box wrench provided for this operation to remove the nozzle, taking care to not damage the elec-
trodes. Fit the new nozzle with the same care. Note: Always check the position of electrodes after having replaced the
nozzle (see illustration). A wrong position could cause ignition troubles.
3,5 mm
6 mm
DESCRIPTION OF CONTROL PAN EL
A - reset key
B - operating lamps (orange=light-oil; green= gas)
C - selector:
OUT = loking of devoices for operating at intermediate outputs
UP = operation at max. output
LOW = operation at min. output
AUTO = automatic operation
D - ON/OFF switch
E - selector:
0 = STOP
1 = light-oil operation
2 = gas operation
3 = automatic operation
F - termal lock-out lamp
G - modulating unit RWF 40 (optional)
E
A
C
D
SAL
SA s.r
HLBT
HLoil
HLgas
SAMA
R
V
R
0=STOP
1=UP
2=LOW
3=AUTO
0 1
RWF 40
0: OFF
1: ON
3=AUTO
2=GAS
1=OIL
0=STOP
SAgG
G
B
F
The control of the detector current shall be carried out by plugging a microampe-
rometer with full scale at 1000 µA (D.C.) in series with the UV-cell. If the detec-
tor current is too low verify the connection between phase and neutral of the bur-
ner and the grounding of the burner itself. Minimum required detector current is
200 µA.
LGB 22
QRA
AGQ1.1A27
1
2
SW
SW
BL
BL
FLAM E D ET EC T O R SYST EM CH ECK
SW = BLACK
BL = BLU