DESCRIPTION OF THE CONTROL PANEL OF THE BURNER
COMBUSTION ADJUSTMENT
WARNING: In order to have a correct combustion and thermal output adjustments, these must be carried out together
with a combustion analysis, to be executed through suitable devices, taking care that the values are the correct ones and
are in accordance with the local safety regulations. The adjustments must be carried out by qualified and skilled techni-
cians authorised by Ecoflam S.p.A.
REMOVING THE BLAST TUBE
POSITION OF ELECTRODES
The control of the detector current shall be carried out by plugging a microampe-
rometer with full scale at 1000 µA (D.C.) in series with the UV-cell. If the detec-
tor current is too low verify the connection between phase and neutral of the bur-
ner and the grounding of the burner itself. Minimum required detector current is
200 µA.
LGB 22
QRA
AGQ1.1A27
1
2
SW
SW
BL
BL
FLAME DETECTOR SYSTEM CHECK
SW = BLACK
BL = BLU
I: 1 st.
II: 2 nd.
SAB
I II
HLgas
R
1: ON
0: OFF
0 1
R
V
R
HLnafta
HLR
HLBT
SARA
SAL
SA s.r
0 I
SAOG
POS 2: GAS
POS 1: NAFTA
POS 0: STOP
POS 3: AUTO
D
F
A -
pulsador de desbloqueo
B -
Indicador del funcionamiento
rojo(Fuel pesado)
rojo(gas)
verde(resistencia)
C - conmutador:
I = potencia mínima
II = potencia máxima
D -
interruptor I / O
E - conmutador:
0 = STOP
1 = funcionamiento a Fuel pesado
2 = funcionamiento a Gas
3 = automatic
F -
Indicador
de bloqueo
G -
interruptor resistencias
B
C
E
G
A
Reset Key
Operating lamps (oran-
ge=heavy oil; green= gas;
red= heater)
Selector switch:
Operation at max. output
Operation at min. output
ON/OFF switch
Selector switch:
0 = Stop
1 = Heavy oil operation
2 = Gas operation
3 = Automatic
Thermal lock-out lamp
Switch AUX heater