Ecoflam MULTIFLAM 200.1 TC VGD 40.065 [7/54] 100 150

Ecoflam MULTIFLAM 200.1 TC VGD 20.503 [7/54] 100 150
7
420010316901 Multiflam 170.1 - 200.1 AB/AB
EN
HEAVY OIL FEEDING
1 - Inlet
2 - Return
3 - Bleed and pressure gauge port
4 - Vacuum gauge port
5 - Pressure adjustment
6 - Nozzle outlet
Oil temperature: Max. 120° in the pump
Inlet and return pressure: 3,5 bar max.
Suction height: 0,5 bar max. vacuum
0,4 bar advised to prevent air separation from oil
PUMP’S PRESSURE / OIL TEMPERATURE DIAGRAM
The gasification of volatile fractions in preheated heavy oil seems to be the main cause of premature fuel
pump wear. To avoid such a problem, adjust pump pressure according to the diagram hereinafter.
1
2
3
4
5
0
50 100 150
bar
Temperatura olio
C°
MAX
MAX
Pressione minima pompa ( bar )
Oil temperature
Pump inlet pressure

Содержание

Похожие устройства

Скачать