Zkteco PL-852D33F-AM — требования к заземлению и расстоянию передачи электричества [39/42]

Zkteco PL-852D33F-AM [39/42] Distance
34
The system must be equipotential grounding. Grounded device must meet double requirements of system anti-jamming and
electrical safety, and can’t be short-circuited or hybrid-circuited with neutral leg of forceful electric power. When system
grounded alone, the impedance of grounded conductor can’t more than 4 ohm, and sectional area of grounded wire can’t
more than 25mm2 wire shorted.
Appendix 4 The relationship between Wire and
Distance
When the Wire diameter size is same and the 24VAC power loss below 10%,Recommended Max.transmission distance.( For AC
powered equipment,Max. Power loss is 10% is allowed.For example,One deceive rated power is 80W,Installed 35 feet from the
transformer <10M> distance,it will need the Min.wire size is 0.80mm ).
0.80 1.00 1.25 2.00
10 283(86) 451(137) 716(218) 1811(551)
20 141(42) 225(68) 358(109) 905(275)
30 94(28) 150(45) 238(72) 603(183)
40 70(21) 112(34) 179(54) 452(137)
50 56(17) 90(27) 143(43) 362(110)
60 47(14) 75(22) 119(36) 301(91)
70 40(12) 64(19) 102(31) 258(78)
80 35(10) 56(17) 89(27) 226(68)
90 31(9) 50(15) 79(24) 201(61)
100 28(8) 45(13) 71(21) 181(55)
110 25(7) 41(12) 65(19) 164(49)
120 23(7) 37(11) 59(17) 150(45)
130 21(6) 34(10) 55(16) 139(42)
140 20(6) 32(9) 51(15) 129(39)
150 18(5) 30(9) 47(14) 120(36)
160 17(5) 28(8) 44(13) 113(34)
170 16(4) 26(7) 42(12) 106(32)
Power W
Distance(m)
Wire Dia. mm