Fluke 1623 [17/30] Ra 4 pole measurements
![Fluke 1623 [17/30] Ra 4 pole measurements](/views2/1004978/page17/bg11.png)
Earth/Ground Tester
Setup
9
R
A
4-pole Measurements
Refer to Figure 5.
A Select function R
A
4-pole.
Display as shown below.
B Connect test leads.
Connect terminals E/C1 and ES/P1 to the earth system to be
measured with the 2 supplied test leads (1.5 m). Place 2 ground
stakes in earth/dirt. Minimum distance between earth electrode
(E/C1), probe (S/P2), and auxiliary earth (H/C2) should be at least
20 m! The ES test lead eliminates the influence of the test leads.
Connect the stakes with the 25 m and 50 m cable reels to H/C2 and
S/P2 as shown below.
C Press START.
The “active” symbol indicates that a measurement is in progress. For
a continuous measurement keep START pressed.
D The symbol “9” indicates a completed measurement. The result is
kept on the display until a new measurement is started or the rotary
switch is turned.
m 02>
m 02>
SESE
H
evitca
E
HS
SE
2P/S
2C/H
1P/SE
1C/E
sulp
V
05
xa
m
2P
S
1P
SE
E
E
HS
SE
FLUKE
1
2
3
4
FLUKE 1623
Earth/Ground Tester
edv004.eps
Figure 5. R
A
4-pole Measurements
Содержание
- Earth ground tester users manual 1
- Fluke corporation p o box 9090 everett wa 98206 9090 u s a 2
- Fluke europe b v p o box 1186 5602 bd eindhoven the netherlands 2
- Limited warranty and limitation of liability 2
- Table of contents 3
- Title page 3
- List of tables 5
- List of figures 7
- Earth ground tester 9
- Introduction 9
- Packing 9
- Safety regulations 9
- Unpacking 9
- Features 10
- Earth ground tester safety regulations 11
- Accessories 12
- Carrying case 12
- Earth ground tester accessories 13
- Models and accessories 13
- Table 2 lists the models and accessories 13
- Inserting batteries 14
- Operating instructions 15
- Pole 3 pole measurements 15
- Ra 2 pole 3 pole measurements 15
- Figure 3 16
- Figure 4 16
- Fluke 1623 16
- Pole measurement 16
- Users manual 16
- Pole measurements 17
- Ra 4 pole measurements 17
- Pole selective earth resistance measurement with current clamp 18
- Ra 3 pole selective earth resistance measurement with current clamp 18
- Pole selective earth resistance measurement with current clamp 19
- Ra 4 pole selective earth resistance measurement with current clamp 19
- Stakeless ground loop measurement 20
- Fluke 1623 22
- Follow the steps in table 4 and refer to figure 9 for steps 1 5 22
- Troubleshooting 22
- Earth ground tester troubleshooting 23
- Specifications 24
- Service 29
- Storage 29
Похожие устройства
- Crown XLS 802 Инструкция по эксплуатации
- Telwin Bimax 4.195 230 V Инструкция по эксплуатации
- Supra SCD-508U Инструкция по эксплуатации
- Beko BPAK 070/BPAK 071 Инструкция по эксплуатации
- Samsung WF8500NHW Инструкция по эксплуатации
- Neff H5950.0 Инструкция по эксплуатации
- Fluke 1625 Инструкция по эксплуатации
- Crown XLS202 Инструкция по эксплуатации
- Blue Weld Combi 4.135 Инструкция по эксплуатации
- Beko BPAK 120/BPAK 121 Инструкция по эксплуатации
- Samsung WF0602NBE Инструкция по эксплуатации
- Supra SCD-507U Инструкция по эксплуатации
- Fluke 1630 Инструкция по эксплуатации
- Neff H5640.0 Инструкция по эксплуатации
- Telwin Bimax 162/1 230 V Инструкция по эксплуатации
- Crown XLS402 Инструкция по эксплуатации
- Supra SCD-506U Инструкция по эксплуатации
- Beko BKK-12 C Инструкция по эксплуатации
- Samsung WF0508NZW Инструкция по эксплуатации
- LG MS-2652T Инструкция по эксплуатации