Using the inverter SinePower
20
Switching to energy-saving mode
You can set the energy-saving mode using the S3 and S4 dip switches. In this way,
the battery you connect to the inverter is not discharged as quickly.
The inverter operates in energy-saving mode as long as the required power is below
the set level. If the required power exceeds the set level, the inverter works in normal
mode.
The values to be set on your inverter can be found in the following table:
Setting net configuration
Using the switch (fig. 2 4) you can define in which net configuration the inverter
shall operate.
Energy-saving mode
DIP switch
S3 S4
Saving mode activated when load < 1 W
Normal mode activated when load > 1 W
Off Off
Saving mode activated when load < 1 W
Inverter shuts automatically down after operation
20 min in saving mode
Normal mode activated when load > 1 W
Off On
Saving mode activated when load < 45 W
Normal mode activated when load > 45 W
On Off
Saving mode activated when load < 45 W
Inverter shuts automatically down after operation
20 min in saving mode
Normal mode activated when load > 45 W
On On
Dip switch
Parameter S5
TN grid
An external downstream circuit breaker (RCD) is
necessary.
Off
IT grid
Operation with one load only or installation of an
external insulation monitor.
National standards shall apply!
On