4.4 Схема подключений
130BD807.10
3-phase
power
input
Switch Mode
Power Supply
Motor
Analog Output
Interface
relay1
relay2
ON=Terminated
OFF=Open
91 (L1)
92 (L2)
93 (L3)
PE
50 (+10 V OUT)
53 (A IN)
54 (A IN)
55 (COM A IN)
0/4-20 mA
12 (+24 V OUT)
13 (+24 V OUT)
37 (D IN)
18 (D IN)
20 (COM D IN)
10 V DC
15 mA 130/200 mA
+ - + -
(U) 96
(V) 97
(W) 98
(PE) 99
(COM A OUT) 39
(A OUT) 42
(P RS-485) 68
(N RS-485) 69
(COM RS-485) 61
0 V
5V
S801
0/4-20 mA
RS-485
RS-485
03
+10 V DC
0/-10 V DC -
+10 V DC
+10 V DC
0/4-20 mA
0/-10 V DC-
240 V AC, 2 A
24 V DC
02
01
05
04
06
24 V (NPN)
0 V (PNP)
0 V (PNP)
24 V (NPN)
19 (D IN)
24 V (NPN)
0 V (PNP)
27
24 V
0 V
(D IN/OUT)
0 V (PNP)
24 V (NPN)
(D IN/OUT)
0 V
24 V
29
24 V (NPN)
0 V (PNP)
0 V (PNP)
24 V (NPN)
33 (D IN)
32 (D IN)
1 2
ON
A53
ON
21
A54
ON=0/4-20 mA
OFF=0/-10 V DC -
+10 V DC
95
P 5-00
21
ON
S801
: Chassis
: Ground
**
240 V AC, 2 A
400 V AC, 2 A
*
Рисунок 4.1 Схема основных подключений
A
= аналоговый, D = цифровой
*Клемма 37 (опция) используется для функции безопасного отключения крутящего момента. Инструкции по установке
функции безопасного отключения крутящего момента см. в Инструкциях по эксплуатации функции безопасного
отключения крутящего момента для преобразователей частоты VLT
®
.
**Не подключайте экран кабеля.
Электрический монтаж Инструкции по эксплуатации
MG16E350 Danfoss A/S © Вер. 10–04–2014 Все права защищены. 15