Danfoss MCD 201-037-T6-xxx [13/24] N control circuits

Danfoss MCD 201-037-T6-xxx [13/24] N control circuits
MCD 200 Design Guide
MCD
201
Control Circuits
2WireControl
A3
A1
A2
N1
N2
START/
STOP
*
380-440 VAC (CV3)
177HA211.10
110-240 VAC (CV3)
OR
24 VAC/VDC (CV1)
A3
A1
A2
N1
N2
START/
STOP
*
(+)
(-)
* Also resets the MCD 201
3WireControl
380-440 VAC (CV3)
A3
A1
A2
N1
N2
START
STOP
*
177HA212.10
A3
A1
A2
N1
N2
START
STOP
*
(+)
(-)
110-240 VAC (CV3)
OR
24 VAC/VDC (CV1)
* Also resets the MCD 201
Functionality
User Adjustments
177HA248.10
70%
60%
50%
40%
30%
10s
Full
Voltage Start
(seconds)
2s
4s
6s
8s 12s
14s
16s
20s
10s
No
Soft Stop
(seconds)
2s
4s
6s
8s 12s
14s
16s
20s
Ramp Down
U
Initial Torque
U
Ramp Up
U
(% U)
1 Initial Torque
Value:
30% - 75% Initial Torque
50%
Function:
Determines the start torque generated by the motor
when the start command is first applied.
Description of choice:
Set so that the motor b egins to rotate as soon
as the start command is given.
U
100%
Initial Torque
(30 - 75%)
177HA249.10
2RampUp
Value:
2 - 20 seconds, Full Voltage
10 seconds
Function:
Determines the time taken fo r voltage to be
ramped up to line voltage.
Description of choice:
Set to optimise motor acceleration and/or start current.
Short ramp times result in quicker acce leration and
higher start currents. Long ramp times result in
slower acceleration and lower start current.
U
100%
Ramp Up
(2 - 20 seconds, Full Voltage Start)
Initial Torque
(30 - 75%)
177HA250.10
3RampDown
Value:
2 - 20 seconds, No Soft Stop
No Soft Stop
Function:
Sets the time of the soft stop voltage ramp. The
soft stop function extends motor deceleration
time by ramping down voltage supplied to the
motor when a stop is initiated.
Description of choice:
Set the ramp time to optimise stopping
characteristics for the loa d.