MCD 200 Design Guide
MCD
202
- the ramp time provides the desired
starting performance
2. On generator set supplies where a gradual increase
in current is required to allow greater time for the
generator set to respond to the increased loading.
In this case make the following settings:
•SetParameter2Current Limit as desired.
•SetParameter3Current Ramp so that:
-theInitial Start Cu rrent is lower level than
the Current Limit
- the ramp time achieves the desired g radual
draw of start current
4 SoftStopRampTime
Value:
2 - 20 sec onds, No Soft Stop
No Soft Stop
Function:
Setsthetimeofthesoftstopvoltageramp. The
soft stop function extends motor de celeration
time by ramping down voltage supplied to the
motor when a stop is initiated.
Description of choice:
Set the ramp time to optimise stopping
characteristics for the load.
Soft Stop
(2 - 20 seconds, No Soft Stop)
U
100%
177HA268.10
5 Motor Trip Class
Value:
2-20,Off
10
Function:
Calibrates the MCD 202 motor thermal model
according to the desired m otor trip class.
Description of choice:
177HA258.10
1000
100
10
1
100 300 500 700 I (% FLC)
t(s)
Class 10
Class 20
Cold Start Curves
20
600
6 Excess Start Time Protection
Value:
2 - 20 seconds, Off
10 seconds
Function:
Sets the maximum allow able start time.
Description of choice:
Set for a period slightly longer than the normal
motor starting time. The M CD 202 w ill then trip
if the start time exceeds normal.
I
100%
200%
300%
400%
Excess Start Time Protection
(2 - 20 seconds, Off- no excess start time protection)
177HA259.10
This provides early indicatio n that the application
conditions ha ve changed or that the motor has
stalled. It can also p rotect the soft starter from being
operated outside its rated start capability.
NB!:
Ensure the Excess Start Time protection setting
is within the MCD 202 rated capability.
7 Phase Rotation Protection
Value:
ANY, FWD
ANY
ANY = Forward & Reverse rotation permitted
FWD = Forward Rotation Only
Function:
Sets the allowable phase rotation sequence
of the incoming supply.
MG.17.C2.02 - VLT is a registered Danfoss trademark
17