Danfoss MCD 201-037-T6-xxx [14/24] N indication

Danfoss MCD 201-037-T6-xxx [14/24] N indication
MCD 200 Design Guide
Ramp Down
(2 - 20 seconds, No Soft Stop)
U
100%
177HA251.10
Indication
1L13L25L3
2T14T26T3
Ready
Run
177HA252.10
LED OFF ON FLASH
Ready No control
power
Ready Starter
tripped
Run Motor not
running
Motor
running at
full speed
Motor
starting or
stopping
Fault Finding
Ready LED Description
x1
Power Circuit Fault:
Check mains supply L1, L2 &
L3, motor circuit T1, T2 & T3
and soft starter SCRs.
x6
Supply Frequency:
Check sup ply frequency is in
range
x8
Network Comms Failure
(between accessory module
and network):
Check network connections
and settings.
x9
Starter Comms Failure (between
starter and accessory m o dule):
Remove and refit accessory
module.