Operation and Display
C220/C420 General Flux Vector Control Inverter User Manual
When the inverter is restarted on power off, the displayed parameters are the
selected parameters before the power off.
3.4 Automatic Tuning of Motor Parameters
To select the vector control running mode ,it must input the nameplate
parameter of the motor accurately prior to the running of inverter, The
C220/C420inverter will select standard motor parameters matching the nameplate
parameter; depending on the motor parameters ,the vector control mode must
acquire the accurate parameters of the controlled motor to ensure the good control
performance the procedures for the automatic tuning of motor parameters are
described below
First, select the command source (F0-04) as the command channel of the
operation panel
Second, input the following parameters in accordance with the actual motor
parameters
Second, input the following parameters in accordance with the actual motor
parameters
F4-01: Rated motor power F4-02: Rated motor voltage
F4-04: Rated motor current F4-05: Rated motor Frequency
F4-06: Rated motor speed
If the motor cannot be completely disconnected with the load, select 2
(complete tuning) in F4-00,and then press RUN key on the keyboard panel, the
inverter will automatically calculate the following parameters