TABLE II – SETTING OF SAFETY AND CONTROL DEVICES
- LCE C-H SERIES
CONTROL DEVICE ACTIVATION DIFFERENTIAL RESETTING
Antifreeze thermostat °C +4 1 Automatic
Maximum safety pressure switch bar 45 -13.5 Manual
Maximum safety pressure switch bar 40.5 -12.2 Manual
Low pressure safety valve bar 29 - -
Minimum pressure switch bar 1.5 +1.0 Automatic
Modulating condensation control bar 18 10
Time lapse between two start-ups of the
same compressor
s 450 - -
Flow meter alarm delay s 20 - -
Low pressure alarm delay s 1 - -
Pump rotation [optional] h 6 - -
Defrost end pressure bar 29 - -
Maximum defrost time s 360 - -
Minimum time between two defrosts s 1800 - -
- LCE F SERIES
CONTROL DEVICE ACTIVATION DIFFERENTIAL RESETTING
Antifreeze thermostat °C +4 1 Automatic
Maximum safety pressure switch bar 45 -13.5 Manual
Maximum safety pressure switch bar 40.5 -12.2 Manual
Low pressure safety valve bar 29 - -
Minimum pressure switch bar 1.5 +1.0 Automatic
Modulating condensation control bar 18 10
Time between two start-ups of same
compressor
s 450 - -
Flow meter alarm delay s 20 - -
Low pressure alarm delay s 1 - -
Pump rotation [optional] h 6
Defrost end pressure bar n/a - -
Temperature differential to activate free-
cooling
°C 3 - Automatic
Water-side safety valve bar 3
Max water-side PN with tank bar 3
Max PN for standard 3-way valve bar 6
Max PN for 3-way poppet valve (optional) Bar 16