Galletti LCE 091 HS [43/64] Cooling mode outdoor air temperature 35 c water temperature 12 c 7 c sound power measured according to standards iso 3741 iso 3744 and en 29614 1 sound pressure measured at...

Galletti LCE 364 HS [43/64] Cooling mode outdoor air temperature 35 c water temperature 12 c 7 c sound power measured according to standards iso 3741 iso 3744 and en 29614 1 sound pressure measured at...
LCE
RG66004766_rev.05
43
Cooling mode: outdoor air temperature 35°C, water temperature 12°C / 7°C
Sound power measured according to standards ISO 3741 - ISO 3744 and EN 29614-1
Sound pressure measured at a distance of 10 m and a height of 1.5 m above the ground in a clear field.
Approx, capacity (kW) 45 50 60 70 80 120
Efficiency Pack 2222 2124 1 2 4 1 24
LCE,,,CS 042 052 062 072 082 091 092 094 101 102 104 121 122 124
Power supply V-ph-Hz
Cooling capacity kW - - 63,3 69,2 76,5 92,2 92,2 - 102,8 103,5 - 124,1 123,6 126,4
Total power input kW - - 24,8 27,7 31,7 33,1 36,2 - 39,5 43,3 - 43,1 46,9 42,9
Rated current input A - - 37,83 46,89 53,33 56,88 61,81 - 67,09 66,7 - 74,13 71,46 73,92
EER - - 2,56 2,5 2,42 2,78 2,55 - 2,6 2,39 - 2,88 2,64 2,94
ESEER - - 3,89 3,93 3,78 3,45 3,88 - 3,4 3,75 - 3,88 4,09 4,09
Maximum current input A - - 60 64 75 91 91 - 101 101 - 119 119 120
Starting current A - - 195 192 200 261 261 - 269 269 - 319 319 247
No, of scroll compressors / circuits - - 2 / 1 2 / 1 2 / 1 2 / 2 2 / 1 - 2 / 2 2 / 1 - 2 / 2 2 / 1 4 / 2
No, of axial fans --44 466- 6 6 - 8 88
Air flow rate m
3
/h - - 21379 21379 21379 30913 30913 - 30913 30913 - 41340 41340 41340
Water flow rate l/h - - 10887 11902 13158 15858 15858 - 17665 17665 21346 21346 21747
Pressure drop, water side kPa - - 46 34 42 31 31 - 38 38 39 41,6 40
Available head, standard pump kPa - - 126 133 119 130 130 - 119 119 108 108 106
Buffer tank dm
3
- - 200 200 200 220 220 - 220 220 - 340 340 340
Expansion tank dm
3
- - 12 12 12 12 12 - 12 12 - 12 12 12
Plumbing connections " - - 2 2 2 2 2 - 2 2 - 2 1/2 2 1/2 2 1/2
Height mm - - 1735 1735 1735 1735 1735 - 1735 1735 - 1735 1735 1679
Length mm - - 2090 2090 2090 2442 2442 - 2442 2442 - 3190 3190 3540
Depth mm - - 1183 1183 1183 1183 1183 - 1183 1183 - 1183 1183 1183
Sound power level dB(A) - - 84,0 84,0 84,0 82,0 86,0 - 82,0 86,0 - 82,0 86,0 82,0
Sound pressure level dB(A) - - 56,0 56,0 56,0 54,0 58,0 - 54,0 58,0 - 54,0 58,0 54,0
Base unit operating weight kg - - 540 570 650 730 730 - 730 730 - 1010 1010 1050
Unit with pump and full tank operating weight kg - - 877 907 987 1138 1138 - 1138 1138 - 1581 1581 1641
400-3-50
90 100
Rated technical data of LCE water chillers, STANDARD version
Approx, capacity (kW) 170 190 210 240 270
290 320 360
Efficiency Pack 1241 2444 4 4 4
444
LCE,,,CS 141 142 144 161 162 164 174 194 214 244 274 294 324 364
Power supply V-ph-Hz
Cooling capacity kW 138,3 137,7 140,3 155,1 154,7 153,4 161,8 186,9 209 237 271,9 296,2 214,3 353,4
Total power input kW 48,3 52,6 47,7 58,7 64 56,1 61,9 77,3 91,1 101,6 11,9 126,8 131,8 138,1
Rated current input A 82,46 89,4 81,61 99,17 107,72 94,99 104,45 128,83 150,97 167,841 189,2 205,14 217,98 227,93
EER 2,87 2,62 2,94 2,64 2,42 2,74 2,61 2,42 2,29 2,3 2,39 2,39 2,38 2,56
ESEER 3,93 4,01 4,1 3,61 3,79 3,75 4,04 3,84 3,84 3,89 3,94 3,91 4,05 4,18
Maximum current input A 131 131 129 137 144 150 136 155 173 196 224 237 251 300
Starting current A 330 330 245 389 396 266 252 310 330 380 403 468 476 497
No, of scroll compressors / circuits 2 / 2 2 / 1 4 / 2 2 / 2 2 / 1 4 / 2 4 / 2 4 / 2 4 / 2 4 / 2 4 / 2 4 / 2 4 / 2 4 / 2
No, of axial fans 8888 8866 6 6 8 8 88
Air flow rate m
3
/h 39890 39890 39890 39890 39890 39890 67672 67672 67672 75478 103511 97902 97902 97902
Water flow rate l/h 23805 23805 24143 26660 26660 26378 27864 32095 35948 40747 46716 50827 53990 60257
Pressure drop, water side kPa4849504242424649505341495541
Available head, standard pump kPa 150 150 147 147 147 148 155 133 147 171 170 152 137 134
Buffer tank dm
3
340 340 340 340 340 340 600 600 600 600 600 600 600 600
Expansion tank dm
3
12 12 12 12 12 12 24 24 24 24 24 24 24 24
Plumbing connections " 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 3 3 3 4 4 4 4 4
Height mm 1735 1735 1679 1735 1735 1679 1847 1847 1847 2247 2330 2330 2330 2330
Length mm 3190 3190 3540 3190 3190 3540 3538 3538 3538 3538 4206 4206 4206 4206
Depth mm 1183 1183 1183 1183 1183 1183 1653 1653 1653 1653 1653 1653 1653 1653
Sound power level dB(A) 82,0 86,0 82,0 82,0 86,0 82,0 87,0 87,0 87,0 87,0 88,0 88,0 88,0 84,0
Sound pressure level dB(A) 54,0 58,0 54,0 54,0 58,0 54,0 59,0 59,0 59,0 59,0 60,0 60,0 60,0 56,0
Base unit operating weight kg 1055 1055 1070 1085 1085 1220 1440 1460 1470 1620 1880 1912 1947 1947
Unit with pump and full tank operating weight kg 1626 1626 1661 1656 1656 1811 2208 2276 2286 2469 2894 2926 2961 2961
160
Rated technical data of LCE water chillers, STANDARD version
140
#RIF!