LCE
RG66004766_rev.05
32
9.2 MAXIMUM PRESSURE SWITCH
The high pressure switch is of the manually reset type and classifiable as category 4 in accordance with
the EEC 97/23 directive. It directly stops the compressor when the discharge pressure exceeds the set
value (see section 5.4).
To verify its efficiency, while the compressors are running, close off the passage of air into the
condensers and check, by referring to the compressor outlet pressure gauge (previously installed),
whether the pressure switch is activated (i.e. the compressors stop) when the set value is reached.
Attention: during this operation, if the safety device fails to activate, the second cascade-
connected pressure switch will step in to shut down the unit. However, in any event you
should be ready to shut off the unit as directed in the section "Stopping the Unit" – see
also section 5.4.
The high pressure switch must be manually reset; this is possible only when the pressure falls below the
value indicated by set differential (see Table II).
9.3 MINIMUM PRESSURE SWITCH
The low pressure switch stops the compressor when the intake pressure falls below the set value for
more than 60 seconds.
The switch is automatically reset when the pressure rises above the value indicated by the set differential
(see Table II); however, the unit will not resume operation until the alarm memory on the microprocessor
control is cleared.
9.4 SERVICE THERMOSTAT
The function of this device is to start and stop the compressors according to the demand for chilled
water, as determined by a sensor placed at the evaporator inlet [water returning from the system].
This device is a function included in the microprocessor control and operates with proportional extension
band that can be set.
9.5 ANTIFREEZE THERMOSTAT
The antifreeze sensor situated at the evaporator outlet detects the presence of excessively low
temperatures and stops the unit. Together with the flow switch and low pressure switch, this device
protects the evaporator from the risk of freezing as a result of faults in the water circuit.
This device is a function included in the microprocessor control.
9.6 ANTI-RECYCLE TIMER
The function of the timer is to prevent excessively frequent compressor starts and stops.
This device is a function included in the microprocessor control.
It sets a minimum time of 300 seconds between two consecutive starts.
Never modify the factory default delay value: wrong settings could cause serious
damage to the unit.
9.7 OIL DIFFERENTIAL PRESSURE SWITCH
LCE units are equipped with orbiting scroll compressors; these compressors do not have a lubricant
pump and therefore no oil differential pressure switch is provided.
Содержание
- Cooling only heat pump and free cooling versions 1
- Contents 3
- Declaration of conformity 5
- Configurations 6
- Efficiency pack 6
- Efficiency packs 6
- The series 6
- Versions 6
- Below is a list of all possible models broken down by efficiency pack 7
- Chiller free cooling f 7
- Configurations 7
- Efficiency pack 1 1 compressor per circuit efficiency pack 4 2 tandem compressors on 2 circuits 7
- Efficiency pack 1 efficiency pack 2 efficiency pack 4 7
- Efficiency packs 7
- Free cooling fluid chillers with free cooling exchange designed to cool water or mixtures of water and an antifreeze agent intended for civil air conditioning and industrial cooling systems lce chillers available in versions with different acoustic designs s l and cooling circuit architectures efficiency pack 1 4 they cover a range of cooling capacities from 44 to 355 kw calculated with reference to standard test conditions of water 12 7 air entering the finned block heat exchangers 35 c and free cooling operating conditions with an air temperature of 5 c and a temperature differential of the finned block heat exchangers of 15 12 c 7
- Standard version s low noise version for a low noise impact l 7
- Versions 7
- Field of application 8
- General information 8
- Inspection conveyance siting 10
- Installation 12
- Ns sh cc v 15
- Electrical connections 17
- Chiller 19
- Start up 21
- Enthalpy h 24
- Operating limits 25
- Setting operating parameters 29
- Lce f series 31
- Table ii setting of safety and control devices lce c h series 31
- Routine maintenance and checks 33
- Decommissioning the unit 36
- Troubleshooting 37
- Water pressure drops 41
- L c e 1 0 4 h q 42
- Technical data summary 42
- Cooling mode outdoor air temperature 35 c water temperature 12 c 7 c sound power measured according to standards iso 3741 iso 3744 and en 29614 1 sound pressure measured at a distance of 10 m and a height of 1 m above the ground in a clear field 43
- Rg66004766_rev 5 43 43
- Cooling mode outdoor air temperature 35 c water temperature 12 c 7 c sound power measured according to standards iso 3741 iso 3744 and en 29614 1 sound pressure measured at a distance of 10 m and a height of 1 m above the ground in a clear field 44
- Rg66004766_rev 5 44 44
- Cooling mode outdoor air temperature 35 c water temperature 12 c 7 c sound power measured according to standards iso 3741 iso 3744 and en 29614 1 sound pressure measured at a distance of 10 m and a height of 1 m above the ground in a clear field 45
- Rg66004766_rev 5 45 45
- Cooling mode outdoor air temperature 35 c water temperature 12 c 7 c heating mode outdoor air temperature 7 c dry bulb and 6 c wet bulb water temperature 40 c 45 c sound power measured according to standards iso 3741 iso 3744 and en 29614 1 sound pressure measured at a distance of 10 m and a height of 1 m above the ground in a clear field 46
- Lce hs 042 052 062 072 082 091 092 094 101 102 104 121 122 124 46
- Rated technical data of lce heat pumps standard version 46
- Cooling mode outdoor air temperature 35 c water temperature 12 c 7 c heating mode outdoor air temperature 7 c dry bulb and 6 c wet bulb water temperature 40 c 45 c sound power measured according to standards iso 3741 iso 3744 and en 29614 1 sound pressure measured at a distance of 10 m and a height of 1 m above the ground in a clear field 47
- Lce hs 141 142 144 161 162 164 174 194 214 244 274 294 324 364 47
- Rated technical data of lce heat pumps standard version 47
- Cooling mode outdoor air temperature 35 c water temperature 12 c 7 c heating mode outdoor air temperature 7 c dry bulb and 6 c wet bulb water temperature 40 c 45 c sound power measured according to standards iso 3741 iso 3744 and en 29614 1 sound pressure measured at a distance of 10 m and a height of 1 m above the ground in a clear field 48
- Lce hl 042 052 062 072 082 091 092 094 101 102 104 121 122 124 48
- Rated technical data of lce heat pumps low noise version 48
- 214 244 274 294 324 49
- Cooling mode outdoor air temperature 35 c water temperature 12 c 7 c heating mode outdoor air temperature 7 c dry bulb and 6 c wet bulb water temperature 40 c 45 c sound power measured according to standards iso 3741 iso 3744 and en 29614 1 sound pressure measured at a distance of 10 m and a height of 1 m above the ground in a clear field 49
- Lce hl 141 142 144 161 162 164 49
- Rated technical data of lce heat pumps low noise version 49
- Cooling mode outdoor air temperature 35 c water temperature 12 c 7 c heating mode outdoor air temperature 7 c dry bulb and 6 c wet bulb water temperature 40 c 45 c sound power measured according to standards iso 3741 iso 3744 and en 29614 1 sound pressure measured at a distance of 10 m and a height of 1 m above the ground in a clear field 50
- Lce hq 042 052 062 072 082 091 092 094 101 102 104 121 122 124 50
- Rated technical data of lce heat pumps quiet super low noise version 50
- 214 244 274 294 324 51
- Cooling mode outdoor air temperature 35 c water temperature 12 c 7 c heating mode outdoor air temperature 7 c dry bulb and 6 c wet bulb water temperature 40 c 45 c sound power measured according to standards iso 3741 iso 3744 and en 29614 1 sound pressure measured at a distance of 10 m and a height of 1 m above the ground in a clear field 51
- Lce hq 141 142 144 161 162 164 51
- Rated technical data of lce heat pumps quiet super low noise version 51
- Summary table of weights 52
- Note for the exact position of every pin please refer to the dimensional drawing enclosed 53
- Upon request lce frame 1 5 units can be fitted with the rubber anti vibration devices below 53
- Note for the exact position of every pin please refer to the dimensional drawing enclosed note for the exact position of every pin please refer to the dimensional drawing enclosed 55
- Ranges from 2 to 4 hz 154 245 cycles min 55
- The eigenfrequency 55
- Upon request lce units can be fitted with the spring anti vibration devices below 55
- The ratings of the spring anti vibration devices featured on the lce frame 1 5 units are show in the diagram below 56
- The ratings of the spring anti vibration devices featured on the lce frame 6 units are show in the the ratings of the spring anti vibration devices featured on the lce frame 6 units are show in the diagram below 56
- 052 062 062 072 072 082 082 091 092 091 092 101 102 57
- 102 121 122 141 142 161 162 094 104 124 144 164 121 122 124 141 142 57
- 161 162 164 174 194 214 214 244 274 294 324 57
- Note identify the model and dimensional frame to use table reported in par 15 57
- Operating weight of lce c water chiller without hydraulic options 57
- Total std weights 57
- Note identify the model and dimensional frame to use table reported in par 15 58
- Operating weight of lce h heat pumps without hydraulic options 58
- 052 062 062 072 072 082 082 91 92 91 92 101 102 59
- 102 121 122 141 142 161 162 094 104 124 144 164 121 122 124 141 142 59
- 161 162 164 174 194 214 214 244 274 294 324 59
- Note combine the weight with the frame identified in par 15 59
- Weight of hydronic modules 2 pumps full buffer tank add to weight of unit 59
- Weight of hydronic modules c h f 59
- 052 062 062 072 072 082 082 091 092 091 092 101 102 60
- 102 121 122 141 142 161 162 094 104 124 144 164 121 122 124 141 142 60
- 161 162 164 174 194 214 214 244 274 294 324 60
- Note combine the weight with the frame identified in par 15 60
- Weight of hydronic modules 1 pump full buffer tank add to weight of unit 60
- Note combine the weight with the frame identified in par 15 61
- Rg66004766_rev 5 61 61
- Weight of hydronic modules 2 pumps add to weight of unit 61
- Weight with 2 pumps to be added to the std weight 61
- Note combine the weight with the frame identified in par 15 62
- Rg66004766_rev 5 62 62
- Weight of hydronic modules 1 pump add to weight of unit 62
- Weight with 1 pump to be added to the std weight 62
- In the case of the dual pump combined operation option the advanced type of microprocessor is mandatory since it controls the switching on of the second pump according to the number of partialization steps required at every moment this means that the unit will operate in a cost effective manner for most of its life given that based on well known analyses chillers operate under a regimen of partialization for 97 of their lifetime 63
- Pumping and storage systems lce units may be equipped with 6 types of pumping systems complete with expansion tank and buffer tanks single pump low lp head single high head pump hp uprated standard pump and back up pump or low head standard pump and back up pump or low head low head pump for combined operation and high head pump for combined operation and in the case of pump systems including a back up pump the microprocessor controls the pumps in such a way as to equally divide the hours of operation changing over the pumps in the event of a fault lce 63
Похожие устройства
- Galletti LCE 244 HQ Технические данные
- Galletti LCE 274 HQ Инструкция по эксплуатации
- Galletti LCE 274 HQ Технические данные
- Galletti LCE 294 HQ Инструкция по эксплуатации
- Galletti LCE 294 HQ Технические данные
- Galletti LCE 324 HQ Инструкция по эксплуатации
- Galletti LCE 324 HQ Технические данные
- Альтоника BASTA BS-911Z Памятка
- Альтоника BASTA BS-911Z Рекомендации по установке
- Альтоника BASTA BS-911Z Руководство пользователя
- Epson WorkForce Pro WF-M5299DW Руководство администратора
- Epson WorkForce Pro WF-M5299DW Руководство пользователя
- Epson WorkForce Pro WF-M5299DWSV Руководство администратора
- Epson WorkForce Pro WF-M5299DWSV Руководство пользователя
- Epson WorkForce Pro WF-M5299DWAV Руководство администратора
- Epson WorkForce Pro WF-M5299DWAV Руководство пользователя
- Epson WorkForce Pro WF-M5299DWLV Руководство администратора
- Epson WorkForce Pro WF-M5299DWLV Руководство пользователя
- Epson WorkForce Pro WF-M5799DWF Руководство администратора
- Epson WorkForce Pro WF-M5799DWF Руководство пользователя