Galletti LCE 244 HQ [63/64] Pumping and storage systems lce units may be equipped with 6 types of pumping systems complete with expansion tank and buffer tanks single pump low lp head single high head...

Galletti LCE 244 HQ [63/64] Pumping and storage systems lce units may be equipped with 6 types of pumping systems complete with expansion tank and buffer tanks single pump low lp head single high head...
LCE
RG66004766_rev.05
63
15.3 PUMPING AND STORAGE SYSTEMS
LCE units may be equipped with 6 types of pumping systems, complete with expansion tank and buffer
tanks:
- single pump (low LP head );
- single high-head pump (HP uprated);
- standard pump and back-up pump (OR – low head);
- standard pump and back-up pump (OR – low head);
- low-head pump for combined operation (AND);
- high-head pump for combined operation (AND);
In the case of pump systems including a back-up pump, the microprocessor controls the pumps in such a
way as to equally divide the hours of operation, changing over the pumps in the event of a fault.
LCE
042 052 062 072 082
091_2_4
Standard type of pump - OR / AND version
Available head, LCE with standard pump (nom. flow rate) OR kPa 118 115 126 133 119 131
Available head, LCE with standard pump (nom. flow rate) AND kPa 90 89 104 113 102 155
Uprated type of pump - OR / AND version
Available head, LCE with uprated pump (nom. flow rate) OR kPa 188 177 183 184 168 181
Available head, LCE with uprated pump (nom. flow rate) AND kPa 176 166 150 148 131 181
Uprated type of pump - OR / AND (FC) version
Available head, LCE F with uprated pump (nom. flow rate) OR kPa 151 131 150 152 129 151
Available head, LCE F with uprated pump (nom. flow rate) AND kPa 139 120 115 116 91 151
Expansion tank dm
3
8 8 8 8 8 12
LCE
101_2
_4
121_2
_4
141_2
_4
161_2
_4
174 194
Standard type of pump - OR / AND version
Available head, LCE with standard pump (nom. flow rate) OR kPa 120 109 152 149 157 136
Available head, LCE with standard pump (nom. flow rate) AND kPa 144 135 120 119 137 130
Uprated type of pump - OR / AND version
Available head, LCE with uprated pump (nom. flow rate) OR kPa 179 189 173 170 189 258
Available head, LCE with uprated pump (nom. flow rate) AND kPa 179 193 181 185 201 194
Uprated type of pump - OR / AND (FC) version
Available head, LCE F with uprated pump (nom. flow rate) OR kPa 113 129 100 78 - 164
Available head, LCE F with uprated pump (nom. flow rate) AND kPa 115 139 116 104 - 121
Expansion tank dm
3
12 24 24 24 - 24
LCE
214 244 274 294 324 364
Standard type of pump - OR / AND version
Available head, LCE with standard pump (nom. flow rate) OR kPa 150 173 170 152 137 131
Available head, LCE with standard pump (nom. flow rate) AND kPa 124 177 178 163 150 143
Uprated type of pump - OR / AND version
Available head, LCE with uprated pump (nom. flow rate) OR kPa 237 293 289 271 256 233
Available head, LCE with uprated pump (nom. flow rate) AND kPa 188 210 210 195 182 177
Uprated type of pump - OR / AND (FC) version
Available head, LCE F with uprated pump (nom. flow rate) OR kPa 128 189 207 175 148 141
Available head, LCE F with uprated pump (nom. flow rate) AND kPa 103 110 132 103 79 72
Expansion tank dm
3
24 24 24 24 24 24
In the case of the dual pump - combined operation option, the advanced type of microprocessor is
mandatory, since it controls the switching on of the second pump according to the number of partialization
steps required at every moment; this means that the unit will operate in a cost-effective manner for most
of its life given that, based on well-known analyses, chillers operate under a regimen of partialization for
97% of their lifetime.