6 Calibrationofcontroldevices
Allthecontroldevicesaresetandtestedinthefactorybeforetheunitisdispatched.However,aftertheunithasbeen
inserviceforareasonableperiodoftimeyoucanperformacheckontheoperatingandsafetydevices.Thecalibration
valuesarereportedinTablesIandII.
All the serv
icing operations performed on the control equipment are considered as
extraordinary maintenance and must be carried out EXCLUSIVELY BY QUALIFIED
PERSONNEL: incorrect calibration values can cause serious damage to the unit and serious
injury to people.
Manyofthefunctioningparametersandcalibrationsofthecontrolsystemsthataffecttheintegrityoftheunitareset
bythemicroprocessorcontrolandareprotectedbypasswords.
TableI‐Calibrationofcontroldevices
Controldevice SetPoint°C Differential°C
Servicethermostat‐C 12 2
Servicethermostat‐H 40 2
TableII‐Calibrationofsafetydevices
Controldevice
Unitof
measurement
Switchingiton Differential Resetting
Antifreezethermostat °C +4 2 Automatic
Maximumpressure
switchcat.IVPED
bar 40.5‐Manual
Lowpressuresafetyvalve
cat.IVPED
bar 29.0‐0/+10%‐
Minimumpressureswitch bar 1.5 1.0 Automatic
Modulatingcondensation
control[optional]
bar 18 10‐
Timebetweentwostart
upsofthesame
compressor
s 480‐
Flowswitchalarmdelay s 20‐
Lowpressurealarmdelay s 1‐
Calibrationofthemaximumpressureswitch
Thehighpressureswitchstopsthecompressorwhendeliverypressureexceedsthecalibrationvalue.Forpoweroutputs
greaterthan140kWpercircuit(namelyLER162insinglecircuitandLEW304indualcircuit)therearetwomaximum
pressureswitches,onesetat40.5baran
dtheotherat45bar.Forsmallersizes,thereisjustonepressureswitchsetto
45bar.