6 Parameter Table
24 I67E-EN V1000 Quick Start Guide
Digital Input Settings
H1-01
to
H1-06
DI S1 to S6
Function
Selection
Selects the function of terminals
S1 to S6.
A list of the major functions can be found at the table
end.
Digital Output Settings
H2-01
DO
MA/MB
Function
Set the function for the relay
output MA-MB-MC.
H2-02
DO P1
Function
Sets the function for the photo-
coupler output P1.
H2-03
DO P2
Function
Sets the function for the photo-
coupler output P2.
Major functions are listed at the end of the table.
Analog Input Setting
H3-01
A1 Signal
Level Sel.
0:0 to +10 V (neg. input is
zeroed)
1:0 to +10 V (bipolar input)
H3-02
A1 Func-
tion Sel.
Assign a function to terminal A1.
H3-03 A1 Gain
Sets the input value in % at 10 V
analog input.
H3-04 A1 Bias
Sets the input value in % at 0 V
analog input.
H3-09
A2 Signal
Level
Selection
0:0 to +10 V (neg. input is zeroed)
1:0 to +10 V (bipolar input)
2:4 to 20 mA (9 bit input)
3:0 to 20 mA
H3-10
A2 Func-
tion Sel.
Assign a function to terminal A2.
H3-11 A2 Gain
Sets the input value in % at
10 V /20 mA analog input.
H3-12 A2 Bias
Sets the input value in % at
0 V / 0 mA / 4 mA analog input.
Analog Input Setting
H4-01
AM
Monitor
Selection
Enter value equal to U1-
monitor values. Example: Enter
“103” for U1-03.
H4-02 AM Gain
Sets terminal AM output voltage
equal to 100% monitor value.
H4-02 AM Bias
Sets terminal AM output voltage
equal to 0% monitor value.
Par. Name Description
Pulse Input Setting (Free. ref. input)
H6-02
RP Input
Scaling
Sets the number of pulses (in
Hz) that is equal to 100% input
value.
H6-03
Pulse Train
Input Gain
Sets the input value in % at pulse
input with H6-02 frequency.
H6-04
Pulse Train
Input Bias
Sets the input value in % at 0 Hz
pulse input frequency.
Pulse Output Setting
H6-06
MP
Monitor
Sel.
Enter value equal to U-
monitor values. Example: Enter
“102” for U1-02.
H6-07
MP Moni-
tor Scaling
Sets the number of output
pulses when the monitor is
100% (in Hz).
Motor Overheat Protection
L1-01
Motor
Overload
Prot. Sel.
Sets the motor overload protec-
tion.
0:Disabled
1:Standard fan cooled motor
2:Standard blower cooled motor
3:Vector motor
L1-02
Motor
Overload
Prot. Time
Sets the motor overload protec-
tion time in min. Normally no
change is necessary.
Stall Prevention
L3-01
Stall
Prevention
Selection
during
Accelera-
tion
0:Disabled - Motor accelerates
at active acceleration rate and
may stall with too heavy load
or too short accel time.
1:General Purpose - Hold
acceleration when current is
above L3-02.
2:Intelligent - Acceleration in the
shortest possible time.
L3-02
Stall Prev.
Level dur-
ing Accel.
Sets the current level for stall
prevention during acceleration.
L3-04
Stall Prev.
Selection
during
Decel.
0:Disabled - Deceleration as
set. OV might occur.
1:General Purpose - Decelera-
tion is hold if DC bus voltage
rises high.
Par. Name Description