Tecorp HC2V9P4018 [122/182] Static parameter auto tuning press the run key to measure the motor parameters p9 6 p9 8

Tecorp HC2V9G47P5 [122/182] Static parameter auto tuning press the run key to measure the motor parameters p9 6 p9 8
High Performance Vector Control/Torque Control Inverter User Manual
100
Chapter 6 Parameter Description
P9.01 ~ P9.04 are used to set the motor parameters driven by the setup inverter and shall be set
properly in accordance with the motor nameplate prior to the use.
Note: The power level of the inverter shall match the motor.
It determines the key motor parameters affecting the running control of the inverter through implementing
the parameter auto-tuning. These motor parameters will be stored in the inverter automatically upon
completion of parameter auto-tuning process till next parameter input or another parameter auto-tuning.
The process of parameter auto-tuning is described as follows:
Input P9.00 to P9.04 properly in accordance with the motor nameplate; set the basic running
frequency P0.15, maximum output frequency P0.11 and maximum output voltage P0.12; set the
acceleration/deceleration time P0.08 and P0.09 properly.
Select the implementation mode of parameter auto-tuning P9.15:
1: Static parameter auto-tuning. Press the run key to measure the motor parameters P9.06 ~ P9.08
automatically.
2: Rotating parameter auto-tuning. Press the run key to measure the motor parameters P9.06 ~
P9.14 automatically.
Press the run key to start the parameter auto-tuning, and P9.15 will be restored to 0
automatically upon completion of auto-tuning process.
Note:
If the motor can be disconnected from the load, it can select rotation auto-tuning (P9.15=2), or it
P9.01 Number of motor poles
2~ 24(4)
P9.02 Rated rotation velocity of motor
0 ~ 30000 rpm(1500rpm)
P9.03 Rated power of motor
0.4 ~ 999.9 kW(Factory)
P9.04 Rated current of motor
0.1 ~ 999.9 A(Factory)
P9.05 Motor no-load current I0
0.1 ~ 999.9 A(Factory)
P9.06 Stator resistance R1
0.000 ~ 65.000 (Factory)
P9.07 Stator inductance leakage L1
0.0 ~ 2000.0 mH(Factory)
P9.08 Rotor resistance R2
0.000 ~ 65.000 (Factory)
P9.09 Mutual inductance L2
0.0 ~ 2000.0 mH(Factory)
P9.10 Magnetic saturation coefficient 1
0.00 ~ 100.00 %(Factory)
P9.11 Magnetic saturation coefficient 2
0.00 ~ 100.00 %(Factory)
P9.12 Magnetic saturation coefficient 3
0.00~100.00 %(Factory)
P9.13 Magnetic saturation coefficient 4
0.00~100.00 %(Factory)
P9.14 Magnetic saturation coefficient 5
0.00~100.00 %(Factory)
P9.15 Parameter auto-tuning
0~2(0)