Yaskawa CIMR-UU2A0192A [31/644] General description

Yaskawa CIMR-UU4A0021F [31/644] General description
1.2 General Description
u
U1000 Model Selection
Refer to Table 1.1 for drive selection depending on Normal Duty (ND) or Heavy Duty (HD) rating.
Note: The models and capacities in shown here are based on standard settings and operation conditions. Higher carrier frequencies and higher
ambient temperatures require derating.
Table 1.1 U1000 Models
Three-Phase 200 V Class Three-Phase 400 V Class
Drive Model
Heavy Duty Rating Normal Duty Rating
Drive Model
Heavy Duty Rating Normal Duty Rating
Rated Output
Current (A)
Rated Output
Current (A)
Rated Output
Current (A)
Rated Output
Current (A)
2o0028
22 28
4o0011
9.6 11
2o0042
28 42
4o0014
11 14
2o0054
42 54
4o0021
14 21
2o0068
54 68
4o0027
21 27
2o0081
68 81
4o0034
27 34
2o0104
81 104
4o0040
34 40
2o0130
104 130
4o0052
40 52
2o0154
130 154
4o0065
52 65
2o0192
154 192
4o0077
65 77
2o0248
192 248
4o0096
77 96
4o0124
96 124
4o0156
124 156
4o0180
156 180
4o0216
180 216
4o0240
216 240
4o0302
240 302
4o0361
302 361
4o0414
361 414
u
Control Mode Selection
Table 1.2 gives an overview of the U1000 control modes and their various features.
Table 1.2
Control Modes and Features
Motor Type Induction Motors Permanent Magnet Motors Comments
Control Mode V/f V/f w/PG OLV CLV OLV/PM AOLV/PM CLV/PM
Parameter Setting A1-02 = 0 A1-02 = 1 A1-02 = 2 A1-02 = 3 A1-02 = 5 A1-02 = 6 A1-02 = 7
Default Setting is
OLV control
(A1-02 =2)
Basic Description V/f control
V/f control
using motor
speed
feedback
Open Loop
Vector control
Closed Loop
Vector control
Open Loop
Vector control
for PM motors
Open Loop
Vector control
for IPM motors
Closed Loop
Vector control
for PM motors
1.2 General Description
YASKAWA ELECTRIC SIEP C710636 04C U1000 Industrial MATRIX Drive Technical Manual
31
1
Receiving

Содержание