Daikin EWYQ007ACV3P [3/15] Specifications

Daikin EWYQ007ACV3P [3/15] Specifications
Chillers R-410A EWYQ-ACV3P
1
2
Hydronic Systems Chillers3
2 Specifications
Fan Type Propeller
Model Quantity 1
Motor
Output
W 53
Dischar ge direction Horizontal
Compressor Type Hermetically sealed swing compressor
Refrigerant oil type FVC50K
Refrigerant oil char ge l 0.75
Model Quantity 1
Model 2YC63BXD#C
Sound Level Sound Power Cooling dBA 62 62 63
Sound
Pressure
Cooling dBA 48 48 50
Heating dBA 48 48 49
Refrigerant
circuit
Refrigerant type R-410A
Refrigerant charge kg 1.7
No of circuits 1
Refrigerant control Inverter
Piping
connections
Water heat exchanger inlet / outlet 1" MBSP
Water heat exchanger drain hose nipple 1/2" FBSP
Notes Nominal cooling capacity is based on the following conditions: evaporator: 12°C/7°C; ambient: 35° C
Nominal heating capacity, heating power input and COP at non- Eurovent conditions: ambient 7°CDB/6CWB;
condensor 30° C/35°C.
Nominal heating capacity, heating power input and COP at Eurovent conditions: ambient 7°CDB/6CWB; condensor
40°C/45°C.
The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value,
depending on the distance and acoustic environment.
2-2 ELECTRICAL SPECIFICATIONS
EWYQ0 05ACV3P EWYQ00 6ACV3P EWYQ00 7ACV3P
Power Supply Name V3
Phase 1
Frequency Hz 50
Voltage V 230
Voltage
Tolerance
Minimum % -10%
Maximum % +10%
Unit Zmax list No requir ements
Maximum Running Current A 19
Recommended fuses according to
IEC standard 269- 2
20
Fan Quantity 1
Phase 1
Voltage V 230
Pump Phase 1
Power input kW 0.13
Voltage V 230
Maximum Running Current A 0.58
Speed Minimum rpm 1050
Nominal rpm 2250
Maximum rpm 2450
Evaporator
Heater Tape
Supply Voltage V 230
Capacity W 75
Voltage
Tolerance
Minimum % -10%
Maximum % +10%
Recommended fuses 25A
Notes Fuse value valid for complete unit
2-1 TECHNICAL SPECIFICATIONS
EWYQ0 05ACV3P EWYQ00 6ACV3P EWYQ00 7ACV3P