Daikin EWWDC11BJYNN [17/21] Sound data

Daikin EWWD550BJYNN [17/21] Sound data
3
1
7
Hydronic Systems • Chillers
17
Chillers • R-134A • EWWD-BJYNN
7 Sound data
7 - 1 Sound level data
Sound pressure level EWWD-BJYNN
NOTES
1 Average sound pressure level rated in accordance to ISO 3744, free field semispheric conditions.
2 The values are according to ISO 3744 and are referred to units without pumps kit.
3 The sound pressure levels are calculated from the sound power levels as per the following formula:
Lp = Lw - 10logS
Lp = Sound pressure level Lw = Sound power level
S = (L + 2d)(W + 2d) + 2(L + 2d)(H + d) + 2(W + 2d)(H + d)
L = unit length in m W = unit width in m H = unit height in m d = distance from the unit in m
Reference source 20 μPa
Unit size
Sound pressure level at 1 m from the unit in free field ( rif. 2 x 10
-5
)
63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz dBA
380
63,5 70,5 80,0 74,5 74,0 68,5 60,5 50,5 78,0
460
64,5 71,5 81,0 75,5 75,0 69,5 61,5 51,5 79,0
550
65,5 72,5 82,0 76,5 76,0 70,5 62,5 52,5 80,0
750
66,5 73,5 83,0 77,5 77,0 71,5 63,5 53,5 81,0
850
67,0 74,0 83,5 78,0 77,5 72,0 64,0 54,0 81,5
900
67,5 74,5 84,0 78,5 78,0 72,5 64,5 54,5 82,0
C10
68,0 75,0 84,5 79,0 78,5 73,0 65,0 55,0 82,5
C11
68,5 75,5 85,0 79,5 79,0 73,5 65,5 55,5 83,0