Daikin EWADC19C-SR [34/96] Electrical specifications

Daikin EWADС12C-SS [34/96] Electrical specifications
34
ELECTRICAL SPECIFICATIONS
EWAD C
-
SR
720
790
880
920
620
MODEL
POWER SUPPLY
Phases
Nr
3
3
3
3
3
3
3
3
Frequency
Hz
50
50
50
50
50
50
50
50
Voltage
V
400
400
400
400
400
400
400
400
Voltage tolerance Minimum
%
-
10%
-
10%
-
10%
-
10%
-
10%
-
10%
-
10%
-
10%
Voltage
tolerance Maximum
%
+10%
+10%
+10%
+10%
+10%
+10%
+10%
+10%
UNIT
Maximum starting current
A
597
642
642
906
953
1007
1010
1055
Nominal running current cooling
A
371
450
518
548
609
654
694
755
Mximum running current
A
462
531
575
639
698
767
837
895
Maximum current for wires sizing
A
506
582
630
700
765
841
916
980
FANS
Nominal running current cooling
A 26 26 26 31 31 36
42
47
COMPRESSORS
Phases
Nr
3
3
3
3
3
3
3
3
Voltage
V
400
400
400
400
400
400
400
400
Voltage tolerance Minimum
%
-
10%
-
10%
-
10%
-
10%
-
10%
-
10%
-
10%
-
10%
Voltage tolerance Maximum
%
+10%
+10%
+10%
+10%
+10%
+10%
+10%
+10%
Maximum running current
A
218
218
231
274
274
274
274
333
333
333
333
398
398
398
398
451
Starting method
---
Y
-
Y
-
Y
-
Y
-
Y
-
Y
-
Y
-
Y
-
EWAD C-SR
H14
MODEL
POWER SUPPLY
Phases
Nr
3
3
3
3
3
3
3
3
Frequency
Hz 50 50 50 50 50 50
50
50
Voltage V 400 400 400 400 400 400 400 400
Voltage tolerance Minimum
%
-
10%
-
10%
-
10%
-
10%
-
10%
-
10%
-
10%
-
10%
Voltage tolerance Maximum % +10% +10% +10% +10% +10% +10% +10% +10%
UNIT
Maximum starting current
A
1068
1241
1292
1344
1346
1389
1434
1447
Nominal running current cooling
A
811
857
954
1002
1075
1158
1179
1238
Mximum running current
A
949
1052
1116
1186
1250
1303
1362
1415
Maximum current for
wires sizing
A
1039
1152
1223
1299
1369
1428
1492
1550
FANS
Nominal running current cooling
A
47
52
52
57
57
57
62
62
COMPRESSORS
Phases
Nr
3
3
3
3
3
3
3
3
Voltage
V
400
400
400
400
400
400
400
400
Voltage tolerance Minimum
%
-
10%
-
10%
-
10%
-
10%
-
10%
-
10%
-
10%
-
10%
Voltage tolerance Maximum
%
+10%
+10%
+10%
+10%
+10%
+10%
+10%
+10%
Maximum running current
A
451
451
333
333
333
398
333
333
398
398
333
398
398
398
398
398
451
451
451
398
451
451
451
Starting method
---
Y
-
Y
-
Y
-
Y
-
Y
-
Y
-
Y
-
Y
-
Fluid: Water
Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
Maximum starting current: starting current of biggest compressor + current of the compressor at 75% maximum load + fans current for the circuit at 75%.
Nominal current in cooling mode is referred to the following conditions: evaporator 12/7°C; ambient 35°C; compressors + fans current.
Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current
Maximum unit current for wires sizing is based on minimum allowed voltage
Maximum current for wires sizing: (compressors full load ampere + fans current) x 1,1.