EUWAC5~10FBZW1
Packaged air-cooled water chillers
4PW61657-1 – 07.2010
Installation and operation manual
2
OPTIONS AND FEATURES
Refer to the engineering data book for the complete list of
specifications, options and features.
Options
Glycol application for chilled water temperature down to –10°C
or –5°C.
BMS-connection MODBUS (optional kit address card
EKAC10C)
(1)
Remote user interface (optional kit EKRUMCA). (Necessary to
additionally install kit address card EKAC10C.)
(1)
Features
Voltage free contacts
- general operation
- alarm
- operation compressor 1
Changeable remote inputs
Following functions can be assigned to a total of 1 digital input.
- remote start/stop
- dual setpoint
Technical specifications
(2)
Electrical specifications
(2)
Options and features
(3)
Options
Glycol application for chilled water temperature down to –10°C
or –5°C. (**)
(**) Do not use internally Zinc-coated or galvanized steel pipes
for the additional waterpiping.
BMS-connection (MODBUS/J-BUS, BACNET)
Remote user controller (optional kit EKRUMCA)
Features
Lower ambient temperature operation (–10°C DB) due to
integrated head pressure control.
Standard operation range
MAIN COMPONENTS (See figure 1)
(1) When EKAC10C is used in combination with remote user controller
EKRUMCA then it is not possible to use the BMS-connection MODBUS.
(2) Refer to the chapter Operating the unit“ or engineering data book for the
complete list of specifications and options.
Model EUWAC 5 8 10
Dimensions HxWxD
(mm)
1345x
795x605
1290x
1125x605
1395x
1275x605
Weight
• Machine weight
(kg)
164 224 261
• Operation weight
(kg)
166 228 266
Connections
•Water inlet
FBSP 1” FBSP 1” FBSP 1”
•Water outlet FBSP 1”
FBSP 1” FBSP 1”
•Water drain
(mm)
25 25 25
Maximal E.S.P.
(*)
(*) E.S.P.=External Static Pressure
(Pa)
100 150 150
Model EUWAC 5 8 10
Power circuit
• Phase 3N~
•Frequency
(Hz)
50
•Voltage
(V)
400
•Voltage tolerance
(%)
±10
(3) Refer to the chapter Operating the unitor engineering data book for the
complete list of specifications and options.
Standard operation range
Protect the water piping against water freezing during winter
period
A
Outdoor ambient temperature (°C DB)
B
Leaving water temperature evaporator (°C)
C
Glycol
D
Water
E
For nominal E.S.P. of 60 Pa (8 Hp) and of 72 Pa (10 Hp)
F
For E.S.P. of 150 Pa (8+10 Hp only)
1 Upper service plate
2 Lower service plate
3 Water inlet connection
4 Water outlet connection
5 Power supply intake
6 Digital controller
7 Drain outlet
8 Low pressure gauge (suction pressure)
9 High pressure gauge (discharge pressure)
10 Air inlet ducting flanges
11 Air outlet ducting flanges
12 Identification plate
B
A
36
43
40
42125
0
0
–5–10–15–20 11 15
40
10
20
50
ZL
ZH
C
D
EE
F
E
F
4PW61657-1_digital_EN.book Page 2 Friday, August 27, 2010 8:09 AM