Daikin EWYP095CAYN [14/392] General data

Daikin EWYP130CAYN [14/392] General data
14 CG-SVX04C-E4
Table 5 - Hydraulic module and buffer tank
EWAP EWAP EWAP EWAP EWAP EWAP EWAP EWAP EWAP EWAP EWAP
EWYP EWYP EWYP EWYP EWYP EWYP EWYP EWYP EWYP EWYP EWYP
060 080 100 120 125 130 160 180 210 240 260
Motor (2) (kW) 2.2 2.2 2.2 4.0 2.2 4.0 4.0 4.0 4.0 5.5 5.5
Rated Amps (2) (A) 4.9 4.9 4.9 4.9 7.5 7.5 7.5 7.5 7.5 11.1 11.1
Motor RPM (rpm) 2900
Water strainer Ø 2" 2
1
/2" 2
1
/2" 2
1
/2" 2
1
/2" 2
1
/2"2
1
/2" 3" 3" 3" 3"
Expansion tank volume (L) 25 25 25 25 25 35 35 35 35 35 35
User volume expansion
capacity (1) (L) 1000 1000 1000 1000 1 000 1400 1400 1400 1400 1400 1400
Antifreeze heater (W) 150
Piping material Steel
Hydraulic Module Weight (kg) 103 108 108 108 108 110 110 114 114 189 189
Water tank volume
(Option) (L) 370 410 410 410 410 570 570 570 570 570 570
Water tank additionnal
shipping height (mm) 400
Water tank additionnal
shipping weight (kg) 396 437 436 436 436 644 644 644 644 644 644
(1) Hydrostatic pressure 3 bar at 45°C with -12°C mini
(2) Dual Pump Option