Chillers • R-407C • EUWY-BZ6Y
Applied Systems • Chillers
12
1
3
3 Specifications
3-2 ELECTRICAL SPECIFICATIONS
EUWY030BZ6Y EUWY035BZ6Y EUWY040BZ6Y EUWY045BZ6Y EUWY049BZ6Y EUWY050BZ6Y
Power Supply Name Y1
Phase 333333
Frequency Hz505050505050
Voltage V 400 400 400 400 400 400
Voltage
Tolerance
Minimum % -10%
Maximum % +10%
Unit Starting Current A 203 215 236 236 236 256
Maximum Running Current A 57.00 69.00 89.00 89.00 89.00 110.00
Compressor Maximum Running Current A 19.00 28.50 28.50 28.50 28.50 19.00
Power factor 0.85 0.85 0.85 0.87 0.85 0.85
Maximum Running Current A 28.50 28.50 28.50 25.50 28.50 28.50
Power factor 0.85 0.85 0.87 0.85 0.85
Maximum Running Current A 18.50 18.50 18.50 18.60 18.70
Power factor 0.85 0.85 0.85 0.87 0.87
3-2 ELECTRICAL SPECIFICATIONS
EUWY060BZ6Y EUWY070BZ6Y EUWY080BZ6Y EUWY090BZ6Y EUWY095BZ6Y
Power Supply Name Y1
Phase 3 3 3 3 3
FrequencyHz5050505050
Voltage V 400 400 400 400 400
Voltage
Tolerance
Minimum % -10%
Maximum % +10%
Unit Starting Current A 278 295 324 344 441
Maximum Running Current A 131.00 140.00 178.00 200.00 216.00
Compressor Maximum Running Current A 28.50 19.00 28.50 28.50 47.00
Power factor 0.85 0.85 0.85 0.85 0.87
Maximum Running Current A 28.50 19.00 28.50 28.50 47.00
Power factor 0.85 0.85 0.85 0.85 0.87
Maximum Running Current A 28.50 19.00 28.50
Power factor 0.85 0.85 0.85
NOTES
1 Nominal cooling capacity at Eurovent conditions: Evaporator 12°C/7°C; ambient 35°C
2 The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value, depending on the distance and acoustic
environment.
3 The sound power level is an absolute value indicating the "power" which a sound source generates.
4 For more details concerning conditional connections, see http://www.daikineurope.com/extranet, select ''DaikinDocumentation'' and select
“conditional connection”. Finally, click on the document title of your choice.