5 Capacity tables
5 - 3 Capacity correction factor
When ethylene glycol is added in the chilled water circuit the following adjustment factors have to be taken in account.
Ethylene glycol adjustment factors
LWE Ethylene glycol Adjustment factors
(%) Water flow rate Pressure drop Power input Cooling capacity
12 30 1.11 1.20 1.005 0.98
5 30 1.11 1.24 1.005 0.98
4 10 1.02 1.08 - -
0 20 1.05 1.19 - -
-4 27 1.08 1.29 - -
-8 33 1.10 1.46 - -
-12 37 1.12 1.62 - -
NOTES
1 A relief valve is located at pump suction limiting water circuit
pressure at 3 bar.
2 Nitrogen pressure inside of the expansion tank must be equal to
the geometric height of the installation + 0.5 bar (in order to
avoid air entering in the water circuit).
3 Expansion tank must be inflated with nitrogen. Pressure must be
checked yearly.
4 For a good pump operation, pump suction pressure must be
between 0.5 and 2.5 bar when pumps runs.
SYMBOLS
LWE: Leaving water evaporator